Product Short Description

Product Overview:​ The ADV551-P50 is a high-density digital output (DO) module in Yokogawa’s CENTUM series. It provides 32 channels of 24 V DC current-sink output, with pulse-width output and time-proportioning ON/OFF output functions. The module installs in the I/O rack of a CENTUM VP, CS 3000 or CS 1000 system and drives field devices such as solenoid valves, indicator lamps, audible alarms and relay coils. Its galvanic isolation and ISA G3 anti-corrosion coating make it suitable for harsh process environments.

Description

Technical Specifications:
  • Model:​ ADV551-P50 (P = with pulse width / time-proportioning output; 5 = no status display, no explosion protection; 0 = basic type)
  • Output Channels:​ 32 channels, grouped every 16 channels on a common minus (−) side
  • Rated Applied Voltage:​ 24 V DC
  • Load Voltage:​ 24 V DC, 50 mA
  • External Power Supply Range:​ 20.4 to 26.4 V DC
  • Output Type:​ Current sink (NPN)
  • Maximum Load Current:​ 100 mA/channel at 26.4 V
  • Leak Current (OFF):​ Max. 0.1 mA
  • Output ON Voltage (max):​ 2 V DC
  • Withstand Voltage:​ 2 kV AC for 1 minute between output signal and system; 500 V AC for 1 minute between commons
  • Output Functions:​ Status ON/OFF, one-shot pulse width, time-proportioning ON/OFF
  • Response Time:​ ≤ 3 ms for status output; ≤ 10 ms for mixed status/pulse outputs
  • Pulse Width:​ 8 ms to 7200 s, resolution 8 ms (with max. 1 ms ON/OFF delay)
  • Current Consumption:​ Max. 700 mA at 5 V DC, 60 mA external power supply
  • Connection:​ Pressure clamp terminal (option /D5S10 with surge absorber), or dedicated cable AKB331, or MIL connector
  • Weight:​ 0.2 kg
  • Operating Temperature:​ –20 °C to +70 °C (ISA G3 option)
  • Hot Swap:​ Supported
Key Features:
  • 32 channels in a single compact module, saving I/O rack space and wiring cost
  • Photoelectric isolation completely separates output channels from the system and from each other, eliminating ground-loop interference
  • Three output modes: status, pulse width, and time-proportioning — covering on/off control, PWM and proportional regulation
  • ISA G3 anti-corrosion PCB coating for chemical, power and offshore applications
  • Hot-swappable in redundant configurations, enabling online replacement without system shutdown
Application Scenarios:​ Valve actuation, motor start/stop control, alarm annunciation, pump control, and any 24 V DC discrete actuation in refineries, power plants, chemical plants and LNG terminals.
Installation Requirements:
  • Insert the module into the correct I/O slot of the CENTUM field control station; confirm the latch engages
  • Use shielded twisted-pair for field wiring; separate from high-voltage cables
  • For the /D5S10 option, the surge absorber terminal block is factory-fitted
  • Verify external 24 V DC supply is within 20.4–26.4 V before energizing
Usage Notes:
  • Observe polarity — the ADV551 is a current-sink (NPN) type; connect field load between +24 V and the output terminal
  • Terminate unused commons appropriately to avoid floating
  • When using pulse-width or time-proportioning mode, ensure the load can tolerate the selected duty cycle
  • Perform periodic inspection of terminal tightness to prevent contact resistance buildup