Product Short Description

Product Name:​ AutoMax / DCS 5000 Common Memory Module (64K)
Product Introduction:​ A common/shared memory module for Reliance Electric AutoMax and DCS 5000 distributed control systems. It provides a shared 64K RAM space for multi-processor configurations, allowing arbitration and data synchronization among multiple processor modules in a rack.

Description

Technical Specifications:
  • Manufacturer:​ Reliance Electric (now part of Rockwell Automation / Baldor)
  • Type:​ Common Memory Module
  • System:​ AutoMax / DCS 5000
  • Memory capacity:​ 64K words (expandable to 128K bytes including 64K registers)
  • Memory type:​ Lithium-battery-backed RAM
  • Battery-backed data retention:​ 600–2000 days with battery installed; 130–400 minutes after battery removal or depletion
  • Backplane current load:​ 1.05 A @ 5 VDC
  • Output frequency:​ 50 kHz (system clock reference)
  • Operating voltage:​ 220 V (rack supply)
  • Status indicators:​ Green “System Watchdog” LED; “Bat.OK” LED for battery voltage
  • Typical installation slot:​ Slot 0 in multi-processor systems (or any even-numbered slot except power supply in single-processor systems; adjacent right slot must remain empty)
  • Environmental:​ Complies with relevant international standards for industrial control
Functional Features:
  • Provides a common memory space shared among multiple processors in a rack.
  • Arbitrates bus access in multi-processor configurations.
  • Stores I/O definitions and system configuration data.
  • Lithium battery backup preserves data during power loss.
  • Watchdog and battery-status LEDs for quick visual diagnostics.
Application Scenarios:​ Multi-processor AutoMax/DCS 5000 racks in metallurgy, paper, power and chemical industries where several processor modules need to share I/O and variable data.
Working Principle:​ The module plugs into the rack backplane and appears as a shared memory segment to all processors. It manages bus arbitration so that only one processor at a time can write to a given memory location, preventing conflicts. The lithium battery maintains RAM contents during power-down.
Installation Requirements:
  • In a multi-processor system, install in slot 0​ of the AutoMax/DCS 5000 rack.
  • In a single-processor system, install in any even-numbered slot except where the power supply resides, leaving the immediately adjacent right-hand slot empty.
  • Ensure the lithium battery is properly installed and charged.
  • Connect to the rack backplane; no separate wiring required.
Usage Precautions:
  • Monitor the “Bat.OK” LED regularly; replace the lithium battery before it fails to avoid data loss.
  • When removing or replacing the battery, note that RAM data is retained for only 130–400 minutes.
  • Do not install in odd-numbered slots in single-processor systems (the adjacent slot constraint must be observed).
  • As a legacy/discontinued product, treat as a critical spare; verify battery health and LED function before deployment.