Product Short Description
Product Introduction
This module is a dedicated bottom-layer baseplate terminal assembly exclusively designed for Alstom heavy-duty steam/gas turbine TRVC series distributed control systems, serving as the physical wiring interface between upper-layer control I/O modules and on-site turbine field sensors and actuators. The Bottom version is installed at the lowest layer of the turbine control rack, integrating multi-channel signal wiring terminals, internal bus conductive copper busbars, signal filtering circuits and lightning surge protection components.
Description
Core Technical Specifications & Performance Parameters
- Rack Installation Position: Bottom fixed mounting layer of Alstom TRVC standard turbine control rack, matched with NRD series upper I/O functional modules
- Integrated Signal Terminal Channels: Total 64 groups of screw locking wiring terminals, divided into 4 independent signal areas: analog input signal terminals, analog output signal terminals, digital DI switch input terminals, digital DO relay output terminals
- Internal Bus Connection Mode: Thick copper conductive busbars integrated inside the baseplate, realizing electrical connection between all wiring terminals and the upper-layer I/O module rear edge connectors
- Signal Filter Circuit Parameters: Each signal channel equipped with RC low-pass anti-interference filter, filter cut-off frequency fixed at 1.2 kHz to suppress high-frequency electromagnetic noise generated by turbine high-power excitation equipment
- Surge Protection Performance: Each channel integrated gas discharge tube lightning surge protection component, maximum withstand surge voltage of 2.5 kV 8/20μs lightning impulse waveform
- Operating Power Supply Range: 24 V DC industrial control power supply, input voltage fluctuation tolerance range of 21.6 V DC ~ 31.2 V DC
- Physical Dimensions: 482.6 mm width (standard 19-inch rack width) × 133 mm height × 210 mm depth, dedicated bottom-layer height size matched with TRVC rack internal slide rail
- Net Weight: 4.2 kg, integrated heavy copper busbars and metal shielding structural components
- Environmental Rating Parameters
- Continuous operating ambient temperature: -10℃ ~ +60℃
- Relative humidity range for operation and storage: 10%RH ~ 90%RH non-condensing
- Shock resistance: 20 g half-sine pulse impact for 11 ms; vibration resistance: 3 g RMS random vibration from 5 Hz to 500 Hz
- Protection grade: IP20 for front panel, only suitable for installation inside fully sealed turbine control electrical cabinets
Function & Feature Highlights
- Specialized bottom-layer integrated terminal baseplate design for Alstom TRVC turbine control racks, centralizing all on-site turbine field signal wiring points to realize unified wiring management, greatly simplifying on-site wiring construction and later equipment maintenance and troubleshooting work
- Four independent partitioned signal wiring areas with physical isolation baffles between different signal types, realizing spatial separation of analog weak current signals and digital strong current signals to eliminate cross-channel electromagnetic crosstalk interference inside the rack
- Each signal channel integrates independent RC low-pass noise filter and gas discharge tube lightning surge protection component; all field signals complete anti-interference filtering and overvoltage surge protection processing on this bottom baseplate before entering upper control modules, effectively reducing the fault damage rate of expensive upper-layer turbine control I/O modules caused by on-site lightning strikes and grid voltage surges
- Thick solid copper internal conductive busbars with full gold-plated surface anti-oxidation treatment; stable low-resistance electrical connection between all wiring terminals and upper I/O modules, avoiding signal measurement drift and control action failure caused by contact resistance increase after long-term rack operation
- Standard 19-inch rack fixed installation structure matched with Alstom TRVC series turbine control system dedicated electrical cabinets; multiple sets of NRD series bottom baseplates can be installed in parallel on the same rack to expand the total number of field signal wiring channels according to the actual I/O quantity of different power plant turbine units
- Front panel equipped with clear silk-screen printed channel number labels, signal type identification marks and wiring sequence standard diagrams; maintenance personnel can quickly find the corresponding channel terminal according to the turbine control system wiring drawing without repeated disassembly and inspection of internal rack components





-500x500.jpg)
Reviews