Description
Technical Specifications
- Bus: VME / VME64, 6U Eurocard
- Protocol: PROFIBUS DP
- Channels: single-channel variants exist; PFB3-VME family supports scanner/master functions
- Interface: RS-485, DB9 PROFIBUS connector
- Baud Rate: 9.6 kbps to 12 Mbps
- Memory: on-board RAM/flash for configuration and cyclic data
- Power: from VME backplane, +5 V typical
- Operating Temperature: 0 °C to +60 °C
- Compliance: CE, industrial EMC, RoHS depending on revision
Functional Features
- Cyclic I/O exchange between VME system and PROFIBUS slaves
- PROFIBUS DP master/scanner functionality
- Diagnostic LEDs for power, run, communication, and fault
- GSD file-based configuration
- Offloads PROFIBUS token and message handling from host CPU
Application Scenarios
- Factory automation
- Motion control systems
- Legacy VME machine controllers
- Steel, automotive, material handling, and test systems
Installation Requirements
- Install only with VME chassis powered off
- Insert into compatible 6U VME slot
- Use shielded PROFIBUS cable
- Terminate both ends of the PROFIBUS segment
- Avoid ground loops; follow VME backplane addressing
Usage Notes
- Do not hot-insert unless chassis and firmware support it
- Use correct GSD/configuration file for connected slaves
- Verify baud rate and station addresses before commissioning