Product Short Description
Product Brief Introduction
Description
Basic Specifications
- Manufacturer: Triconex (Schneider Electric Industrial Automation)
- Product Series: Tricon TMR Safety System
- Product Type: Digital Output Module (16-Channel, 115 VAC, Opto-Isolated)
- Output Configuration: 16 Points, Non-Commoned, Isolated
- Compatibility: Tricon Main/Expansion/RXM Chassis
- System Architecture: Full TMR (Triple Modular Redundancy) Compliant
Electrical Specifications
- Nominal Field Output Voltage: 115 VAC
- Recommended Input Voltage Range: 90–155 VAC
- Frequency Range: 47–63 Hz
- Output Current per Point: 2 A Continuous
- Maximum Surge Current per Cycle: 12 A
- Voltage Drop per Point: ≤ 3 V
- Leakage Current at 60 Hz: ≤ 2 mA
- Chassis Leakage at 60 Hz: ≤ 4 mA
- Fusing: 3 A Fast-Acting Fuse per Channel (Field Side)
- Isolation Voltage: 1500 VDC (Point-to-Point), 2500 VDC (Point-to-Base)
- Logic Power Supply: 5 VDC (Internal System Power)
Environmental Specifications
- Operating Temperature: -40 °C ~ +70 °C
- Storage Temperature: -40 °C ~ +85 °C
- Relative Humidity: 5% ~ 95% (Non-Condensing)
- Vibration Resistance: Industrial Grade (Compliant with IEC 60068-2-6)
- Shock Resistance: Industrial Grade (Compliant with IEC 60068-2-27)
- Safety Certification: IEC 61508 SIL 3, ISA-S84.01, CE Certified, UL Certified
Mechanical Specifications
- Form Factor: Standard Tricon Chassis Slot
- Physical Dimensions: Compliant with Tricon Module Form Factor
- Weight: Industrial-Grade Module Weight
- Mounting: Hot-Swappable, Plug-and-Play Slot Installation
Functional Characteristics
-
TMR Fault-Tolerant Architecture
Three independent channels execute identical logic and vote on outputs. Any single channel fault is isolated without system shutdown, ensuring continuous operation and high availability.
-
16 Independent Isolated Output Channels
Each channel is optically isolated and individually fused, preventing fault propagation between channels and enhancing system robustness.
-
Comprehensive Supervision & Diagnosis
- Per-Channel Supervision: Monitors load status, fuse condition, and circuit integrity.
- Module Status Indicators: Clear LEDs for Module OK, Fault, and Active states.
- Field Alarm Indicators: Dedicated LEDs for Load/Fuse faults per channel.
- System Integration: Transmits diagnostic data to the Tricon controller for predictive maintenance and alarm logging.
-
High-Reliability Field Interface
115 VAC output with 2 A continuous rating and 12 A surge capability directly drives contactors, relays, solenoids, and other AC field devices. Opto-isolation protects the system from field-side transients and noise.
-
Hot-Swappable & Maintenance-Friendly
Supports online replacement without powering down the entire safety system, minimizing downtime and reducing maintenance complexity.
-
Color-Coded Identification
Green color coding for easy visual identification in industrial racks, simplifying installation, maintenance, and troubleshooting.
Application Scenarios
-
Oil & Gas Industry
Wellhead emergency shutdown (ESD) systems, pipeline valve control, gas compressor safety interlocks, and production process sequence control.
-
Petrochemical & Refining
Reactor heater control, furnace burner management systems (BMS), distillation column valve actuation, and flare system safety monitoring.
-
Power Generation
Boiler feedwater pump control, turbine auxiliary system actuation, generator protection system interlocks, and emissions control equipment.
-
Chemical Processing
Pressure relief valve (PRV) control, reactor agitator actuation, cooling tower fan control, and hazardous material handling systems.
-
Metallurgy & Mining
Smelter furnace safety interlocks, conveyor belt valve control, ore processing equipment actuation, and blast furnace gas systems.
-
General Industrial Safety
All high-hazard process control applications requiring SIL 3 safety integrity, including fire protection systems, emergency ventilation, and critical machinery safety interlocks.