Product Short Description
Product Name: TMEICA ARND-3115A18 — Digital Automatic Voltage Regulator, Enhanced Variant
Product Overview: The TMEICA ARND-3115A18 is an advanced digital AVR excitation controller, an upgraded variant of the ARND-3110 platform. The “A18” suffix denotes a specific firmware/hardware configuration with enhanced communication and protection features.

Description
Technical Specifications:
- Model: ARND-3115A18
- Type: Digital AVR — Automatic Voltage Regulator
- Application: Brushless excitation, synchronous generators
- Input Signals: Generator PT voltage, generator CT current, frequency, start/stop, PSS input, remote setpoint
- Output: Programmable firing pulses (6-pulse or 12-pulse)
- Voltage Regulation Accuracy: ±0.25% (steady state) — superior to ARND-3110
- Response Time: < 10 ms (improved transient response vs. 3110)
- Firing Angle Range: 0°–180°, resolution 0.1°
- Communication: RS-485 Modbus RTU, Ethernet TCP/IP (built-in)
- Remote Setpoint: 4–20 mA or 0–10 VDC analog input
- Power Supply: 110/220 VAC, 50/60 Hz, or 24 VDC
- Operating Temperature: -20°C to +55°C (extended range vs. 3110)
- Protocols: IEC 61850 (optional), DNP3.0 (optional)
- Dimensions: Standard panel-mount, 1/4 DIN or full DIN
- Weight: Approximately 1.8 kg
- Compliance: IEC 60034, IEEE 421.5, IEC 61850
Functional Features:
- All features of ARND-3110 plus:
- Built-in Ethernet port for SCADA integration (no external gateway needed)
- Dual voltage regulator channels (main + backup) with automatic transfer
- Event logging: 100 events with timestamps
- Self-diagnostic with fault code display
- Adaptive PID with auto-tuning
- Load compensation function
- Harmonic monitoring (up to 15th harmonic)
Structural Characteristics:
- Enclosure: Die-cast aluminum, IP40 rating (higher than 3110’s IP20)
- Terminals: Spring-clamp terminals for faster wiring
- Display: 8-character LCD with backlight (upgraded from 4-digit LED on 3110)
- Status LEDs: Run, Fault, Comm, Firing, Sync
Working Principle: Same core principle as ARND-3110 — digital PID control of SCR firing angle. The ARND-3115A18 adds a second independent control channel that runs in parallel. If the primary channel fails, the backup channel takes over within one cycle (< 16 ms at 60 Hz). The Ethernet interface allows direct Modbus TCP or IEC 61850 MMS communication with plant DCS/SCADA. The adaptive PID auto-tunes gains based on observed system response during commissioning.
Advantages:
- Dual-channel redundancy — highest availability in the ARND series
- Ethernet native — eliminates need for protocol converter
- Extended temperature range for harsh environments
- Harmonic monitoring helps detect generator winding faults early
Applicable Industries: Critical power generation (data centers, hospitals, military), large hydro stations, combined cycle gas turbines, industrial cogeneration
Installation Requirements:
- Same as ARND-3110 with additions:
- Ethernet cable: Cat5e or better, max 100 m to switch
- Dual PT inputs required for redundancy (two separate PT circuits)
- Shielded firing pulse cables, max 50 m
- Ground impedance: < 0.5 Ohm for critical installations
Usage Precautions:
- Configure redundancy mode (active/standby or parallel) before commissioning
- Update firmware via Ethernet only — do not use RS-485 for firmware updates
- Verify both PT circuits independently before enabling dual-channel mode
- Clean air filter on enclosure every 6 months in dusty environments




Reviews