Product Short Description
Thermon TC202A-SSR15B-240-F-P3
This is a configured version of the Thermon TC202A heat-tracing control and monitoring module. Public catalog sources more commonly list the option string as TC202A-SSR15B-120/240-F-P3, so the exact interpretation of the supplied 240 designation should be confirmed against the nameplate or original order code.
Description
Product Name and Category
TC202A Dual-Circuit Heat-Tracing Control and Monitoring Module
The module is part of a microprocessor-based heat-trace control system.
Product Introduction
The TC202A controls and monitors electrical heat-tracing circuits. It uses temperature sensing to regulate heating and provides alarm or monitoring functions for industrial piping, vessel, and process-temperature systems. Multiple modules can be installed in a common enclosure.
Technical Specifications
- Heat-tracing circuits: 2
- Module supply options: 110–120 VAC or 208–240 VAC
- Module power consumption: 6 W
- Sensor inputs: 2 three-wire 100 Ω platinum RTDs
- Control range: –40 to 500 °C
- Control resolution: 1 °C
- Current monitoring/alarm range: 0.0–30.0 A
- Ground-fault detection range: 30–150 mA
- Self-test interval: programmable from 2 to 99 hours
- Operating temperature: –40 to 60 °C
- Maximum storage temperature: 70 °C
- Data storage: EEPROM
- Module dimensions: 222 × 130 × 67 mm
Functional Features
- Control and monitoring of two independent heat-tracing circuits.
- RTD-based temperature measurement.
- Power-level control with programmable output.
- Ground-fault and overcurrent monitoring where configured.
- Alarm capability through integral relays.
- Modular design for installation in a common enclosure.
- Digital display and communication capability in the broader TC202A product family.
Application Scenarios
- Freeze protection of pipes and valves.
- Temperature maintenance for process lines.
- Industrial plants, including oil and gas, chemical, and power facilities.
- Marine and offshore installations.
- Equipment skids and traced instrument piping.
Performance Parameters
The public TC202A family description shows per-circuit control capability up to 30 A and controlled output voltages from 110–480 VAC, but these are family-level figures. They should not be assumed to define the exact rating of every SSR15B-240-F-P3 configuration without the original specification sheet.
Material Composition
Specific materials for this configuration are not published. A typical module consists of a printed circuit assembly, electronic control and relay or SSR switching components, terminal blocks or connectors, and a protective housing or bezel. The enclosure material depends on the complete assembly and has not been verified.
Structural Characteristics
The TC202A is a modular electronics assembly designed to be installed in a suitable field enclosure. It includes sensor input terminals, heater or load control outputs, power input, and monitoring or communication interfaces. More than one module can share a common enclosure.
Working Principle
Each RTD measures process or heater temperature and sends the signal to the module. The microprocessor compares the measured value with the configured setpoint and control logic. The output stage then switches or regulates power to the associated heat-tracing circuit. Alarms are generated when current, ground-fault, temperature, or sensor conditions exceed configured limits.
Installation Requirements
- Install in an enclosure and environment compatible with the complete configured assembly.
- Verify the module supply voltage before connection.
- Use the correct RTD type and three-wire sensor configuration.
- Keep sensor cables separated from high-current heater cables where practicable.
- Install according to national electrical codes and Thermon project specifications.
- Confirm hazardous-area approvals before using the equipment in classified locations.
Usage Precautions
- Electrical heat tracing involves shock, burn, and fire hazards.
- Only qualified personnel should install, adjust, or service the module.
- Do not rely on the control module as the sole overcurrent or ground-fault protection without verifying the full system design.
- Confirm that the heater cable, circuit breaker, sensor, and module output are correctly matched.
- Protect the module from moisture, condensation, corrosion, vibration, and excessive heat.
- Verify the 120/240 or 240-only supply interpretation on the original order documentation.





Reviews
There are no reviews yet.