Product Short Description
Product Overview:
The Siemens 505-CP2572 is a TCP/IP Ethernet communication module that logs into a TI 505 I/O rack as a special function module. It enables a 505-series PLC to exchange data over Ethernet using connection-oriented (TCP) or connectionless (UDP) services, and provides a PLC logic interface for message-based communication.
Description
Technical Specifications:
-
Manufacturer: Siemens
-
Order Number: 505-CP2572
-
Product Line: TI 505
-
Protocol Stack: TCP/IP (TCP & UDP)
-
Physical Layer: 10 Mbit/s, half-duplex
-
Front-panel Port: AUI, DB-15 female (per IEEE 802.3 10Base5)
-
Interface to PLC: 2 WX words + 6 WY words (special function module login)
-
Command Slots: 4 independent command blocks in V-memory
-
Replacement Product: CP 1434 TF (TI 505)
-
Application-layer: TCP-based send/receive (S/R)
Key Features:
-
Send/receive messaging via PLC ladder logic using WX/WY words and V-memory command blocks
-
Four concurrent command slots for parallel Ethernet transactions
-
Standard Berkeley Socket / Winsock-compatible TCP/IP stack
-
Works over local Ethernet or WAN links
-
AUI port requires an external transceiver (MAU) or AUI-to-UTP converter for 10Base-T
Application Scenarios:
Legacy TI 505 PLC Ethernet integration, HMI/SCADA communication, peer-to-peer 505 PLC messaging, and migration paths to newer Siemens CP modules.
Installation & Usage Notes:
-
Always verify the physical module version, firmware version, and the applicable “Appendix: New Features” document version – mismatches are common in field units.
-
For AUI-connected CP2572, hard-code 10 Mbit/s, half-duplex on the connected switch/hub for reliable operation.
-
Command blocks must be contiguous V-memory words; size them per the chosen command.
-
Use WY words to trigger command execution and WX words to monitor status.
-
When migrating, consider the CP 1434 TF replacement.





Reviews