Product Short Description
Product Name Closed Loop Hall Effect Current Transducer
Product Introduction The LEM LF1005-SSP16 is a closed-loop compensated current transducer utilizing Hall effect technology. It provides accurate, galvanically isolated measurement of AC, DC, and pulse currents for industrial and railway power system applications.
Description
Technical Specifications
- Nominal Primary Current: 1000 A RMS
- Measuring Range: 0 to ±2100 A
- Secondary Nominal Current: 200 mA
- Conversion Ratio: 1:5000
- Supply Voltage Range: ±15 V to ±24 V DC (±10%)
- Accuracy Class: ±0.4% at 25°C
- Linearity Error: <0.1%
- Response Time: <1 µs to 90% of final value
- Frequency Bandwidth: DC to 150 kHz
- Primary Aperture: 40.5 × 13 mm rectangular
- Secondary Connector: JST B 3P-VH connector
- Operating Temperature Range: -40°C to +85°C
- Weight: 600 g
Functional Features
- Closed-loop null-balance Hall effect principle delivers high accuracy and fast response
- Full galvanic isolation between primary and secondary circuits
- Excellent linearity and low temperature drift across operating range
- Wide frequency bandwidth supports DC to high-frequency AC current measurement
- High immunity to external magnetic field interference
- Robust overload capability for transient fault conditions
Application Scenarios
- Industrial variable speed drives and motor control systems
- Railway traction and auxiliary power monitoring
- Power supply and power converter current monitoring
- Battery management and DC power system measurement
- Renewable energy generation and grid integration systems
Material & Construction
- Flame-retardant plastic housing compliant with UL 94-V0
- Laminated magnetic core with precision air gap for Hall element placement
- Potted internal electronics for vibration and moisture resistance
- Integrated electrostatic shield between primary and secondary circuits
Operating Principle
- Primary current flowing through the transducer aperture generates a magnetic field concentrated by the magnetic core.
- A Hall effect sensor positioned in the core air gap detects the magnetic field and produces a proportional voltage signal.
- A secondary compensation coil generates an opposing magnetic field that cancels the primary field, maintaining zero flux in the core (closed-loop null balance).
- The resulting secondary current is directly proportional to the primary current, scaled by the winding turns ratio.
Installation Requirements
- Panel mount installation with appropriate mounting hardware
- Pass primary conductor through the transducer aperture centered in the opening
- Connect secondary output to measurement circuitry via the JST connector
- Connect DC power supply with correct polarity and adequate filtering
- Maintain adequate clearance for high-voltage primary circuit safety
Certifications EN 50155 railway compliant, UL recognized, CE marked





Reviews