Description
Technical Specifications
- Manufacturer: ICS Triplex
- System: Trusted
- Architecture: TMR with 2-out-of-3 voting
- Input Channels: 40 DC inputs
- Nominal Input: 24 V DC
- Operating Range: 18 to 32 V DC
- Groups: 8 groups, 5 inputs per group
- Input Current: approximately 6 mA per channel
- Isolation: optical isolation, high-voltage barrier
- SOE Resolution: 1 ms
- Hot Swap: supported
- Safety: IEC 61508 SIL 3
- Operating Temperature: 0 °C to +60 °C typical; some listings -40 °C to +70 °C
- Humidity: up to 95% non-condensing
Functional Features
- Triple redundant input paths
- Open-circuit and short-circuit detection
- Sequence of Events logging
- Continuous self-diagnostics
- Channel status LEDs
- Online replacement without process shutdown
Working Principle
Each field input is read by three parallel circuits. The module compares results and uses 2oo3 voting to reject faulty channels, ensuring safe and continued operation.
Application Scenarios
- Emergency Shutdown Systems
- Fire and Gas systems
- Burner Management Systems
- Turbine and compressor protection
- Critical interlock loops
Structural Characteristics
- Plug-in Trusted I/O module
- Front-panel LEDs
- Field wiring terminals
- Triplicated input electronics
- Inter-Module Bus interface
Installation Requirements
- Install in compatible Trusted controller chassis
- Verify field device sourcing/sinking type
- Use correct 24 VDC field power groups
- Follow ICS Triplex wiring and grounding rules
Usage Notes
- Only trained personnel should maintain safety I/O
- Validate E-stop and interlock logic after replacement
- Do not bypass voting/diagnostic functions
- Keep firmware/config compatible with system version