Description
Technical Specifications
Bus type: LonWorks
Relay outputs: 6
Relay type: SPDT
AC load: 19 to 250 VAC
DC load: 1 to 24 VDC
Total load: 12 A resistive
NO contact load: 4 A resistive or inductive
NC contact load: 2 A resistive, 1 A inductive
Minimum load: P > 50 mW
Terminal socket: XS824-25
Optional accessory: XS812-RO
Manual override version: XFLR824A
Functional Features
Six isolated relay outputs
Yellow LED per output
Configurable fail-safe position: hold, off, on
Can be configured for floating control with paired relays
Manual override version gives local output forcing
LonWorks integration with Excel 800 controllers
Application Scenarios
HVAC actuator control
Damper and valve switching
Pump control
Fan starter control
Building services automation
Lighting or auxiliary relay control
Structural Characteristics
Pluggable relay output module
Terminal socket carries field wiring
Cross connector for bus and auxiliary power
Swivel label for channel identification
LED indication on each output
Installation Requirements
Mount on compatible XS824-25 terminal socket
Size relay load within contact rating
Use snubber or suppression for inductive loads
Provide correct AC/DC supply to controlled device
Separate low-voltage control wiring from mains where required
Usage Notes
Do not exceed 12 A total relay load
Inductive AC loads reduce relay contact life
Configure communication-loss behavior before commissioning
Manual override must be returned to automatic mode after service
Replace relay module only with power removed from controlled circuit where safety rules require it