Description
Product Brief Introduction
FC-RPB2N12 is a 12-slot standard power distribution backplane dedicated to Honeywell Safety Manager SIS system cabinet, providing shared redundant 24VDC safety power bus and high-speed safety communication bus interface for FC series CPU, I/O, power supply and cooling fan modules. It undertakes power distribution, bus signal transmission and module mechanical fixed support integrated functions for 12-slot SIS rack.
Technical Specifications & Core Performance Parameters
- Slot Capacity: 12 standard FC series module installation slots
- Bus Power Distribution Capacity: Maximum total output 240W matched with FC-PSU-UNI2450U power supply
- Communication Bus Rate: Safety dedicated backplane bus 8Mbps transmission rate
- Power Bus Isolation: Per-slot independent overcurrent fuse protection circuit
- Mechanical Load Bearing Capacity: Maximum single slot module weight 1.2kg
- Physical Dimension: 620mm (L) × 110mm (W) × 30mm (D)
- Net Weight: 2.1kg
- Operating Temperature Range: -20℃ ~ +70℃ cabinet internal
Material Composition
- Backplane Base Frame: Cold-rolled steel stamping forming with anti-corrosion spraying
- Bus Circuit Board: Thick copper layer multi-layer FR4 PCB for high-current power transmission
- Slot Gold-Plated Connector: Phosphor copper alloy thick gold plating anti-oxidation contact pin
- Overcurrent Protection Fuse: Slow-blow industrial safety fuse per slot
Structural Features
- Integrated 12 standard slide-in module slot layout, uniform mechanical positioning guide rail for all FC series modules
- Dual redundant 24VDC power bus copper layer inside backplane, dual power supply parallel current-sharing access terminal
- Independent high-speed safety communication bus signal trace separated from power bus circuit to eliminate electromagnetic crosstalk
- Each slot matched independent overcurrent fuse, single slot short circuit does not affect other modules power supply
Working Principle
- 24VDC safety power output from FC-PSU-UNI2450U power supply module accesses backplane dual redundant power bus copper layer
- Power bus distributes stable 24VDC power to each 12 installation slot through independent slot fuse circuit
- Safety main processor FC-QPP-0001 transmits digital signal via backplane dedicated communication bus trace to all I/O modules
- Per-slot fuse circuit cuts off single-slot power supply immediately when short-circuit overload fault occurs, isolate fault slot without system wide power failure
- Mechanical positioning rail ensures each module slide-in accurate docking of power and communication contact pins
Function Features
- 12-slot integrated power and communication bus distribution, realize centralized rack wiring simplification
- Dual redundant internal power bus supports dual power supply parallel redundant configuration
- Per-slot independent overcurrent fuse protection, fault isolation without whole rack power outage
- Unified mechanical positioning guide rail compatible with all FC series hardware modules
- High-speed isolated communication bus eliminates power circuit interference to safety signal transmission
Advantage Highlights
- Integrated power distribution + communication bus + mechanical support three-in-one design, reduce cabinet internal wiring quantity by 60%
- Per-slot independent fault isolation protection avoids single module short-circuit causing entire SIS system shutdown
- Dual redundant power bus design supports hot standby dual power supply configuration to improve system power supply reliability
- Thick copper layer backplane circuit bear high total output power without voltage drop loss
- Uniform slot mechanical standard eliminate module installation adapter bracket requirement
Applicable Industries
All Honeywell Safety Manager SIS system 12-slot standard cabinet supporting backplane, matching petrochemical, natural gas, chemical plant safety control cabinet
Installation Requirements
- Fixed horizontally inside Safety Manager standard cabinet rear wall with 4 M6 stainless steel fixing bolts
- Connect FC-PSU-UNI2450U power supply DC output terminal to backplane power access copper bar with 1.5N·m standard torque
- Maintain 50mm vertical ventilation gap between backplane and cabinet rear wall for heat dissipation
- All slot modules slide fully into rail until front panel locking buckle clicks into fixed position
- Cabinet safety ground wire connect backplane metal frame dedicated grounding terminal
Usage Precautions
- Forbid replacing slot fuse with non-original overcurrent rated fuse, will lose single-slot fault isolation protection function
- Do not install overweight non-standard modules exceeding 1.2kg single slot load limit
- Clean backplane slot gold-plated contact pin dust with anhydrous alcohol every 12 months
- Avoid bending, squeezing backplane circuit board during module disassembly and assembly
- When single slot fuse blown, cut off rack power supply before fuse replacement operation