Product Short Description

Product Introduction:
The Honeywell 1226-9001 is a fixed-mount single-gas toxic gas transmitter designed for continuous area monitoring of specific hazardous gases in industrial environments. It provides a 4–20 mA output with two alarm relays for safety interlock and evacuation signaling. The unit features a catalytic bead or electrochemical sensor depending on gas type.

Description

Technical Specifications:

  • Part Number: 1226-9001
  • Gas Detected: Carbon Monoxide (CO) — 0–500 ppm range (confirm specific gas variant)
  • Sensor Type: Electrochemical (CO-specific)
  • Output: 4–20 mA (loop-powered, 2-wire)
  • Alarm Relays: 2 SPDT relays — 2 A @ 30 VDC / 250 VAC
  • Alarm Setpoints: Low Alarm, High Alarm (programmable)
  • Accuracy: ±3 ppm or ±5% of reading (whichever is greater)
  • Response Time (T90): < 30 seconds
  • Operating Temperature: -40°C to +55°C (-40°F to +131°F)
  • Operating Humidity: 0–95% RH (non-condensing)
  • Enclosure Rating: NEMA 4X / IP66 (weatherproof)
  • Power Supply: 18–30 VDC
  • Process Connection: 3/4″ NPT conduit entry (bottom)
  • Dimensions: 178 mm × 127 mm × 95 mm
  • Weight: 1.2 kg (2.6 lb)

Functional Features:

  • Dual alarm relays with independent setpoints
  • 4–20 mA output for DCS/PLC integration
  • Non-intrusive calibration via magnet or HART
  • LED indicators: Power, Alarm 1, Alarm 2, Fault
  • Fault relay for sensor failure detection

Performance Parameters:

  • Sensor Life: 2 years (CO electrochemical)
  • Warm-Up Time: < 60 seconds
  • Zero Drift: < ±2 ppm per month
  • EMC: EN 61326, FCC Part 15 Class A
  • Certifications: UL 2075, CSA C22.2, ATEX Zone 2 (if applicable)

Structural Features:

  • UV-stabilized polycarbonate housing
  • 3/4″ NPT conduit entry with gland
  • Terminal block cover with gasket seal
  • Wall-mount bracket included

Working Principle:
CO gas diffuses through a membrane into the electrochemical cell, where it is oxidized at the working electrode, generating a current proportional to gas concentration. The electronics convert this current to a 4–20 mA signal. When concentration exceeds programmable setpoints, the alarm relays activate.

Key Advantages:

  • NEMA 4X / IP66 rating for outdoor and corrosive environments
  • Dual relays enable staged alarm response (warn + evacuate)
  • 2-year sensor life reduces maintenance cost
  • HART-compatible for remote configuration

Applicable Industries: Oil and gas, chemical plants, refineries, wastewater treatment, mining, confined space monitoring

Installation Requirements:

  • Mount 1.5–3.0 m above floor (CO is near-neutral buoyancy)
  • Use shielded twisted-pair cable for 4–20 mA signal
  • Loop resistance: 100–600 Ω
  • Conduit entry must use provided NPT gland

Usage Notes:

  • Bump test sensor monthly with calibration gas
  • Full calibration every 6 months or per regulatory requirement
  • Replace sensor when “Fault” LED illuminates
  • Do not paint or coat the sensor window

Reviews

There are no reviews yet.

Be the first to review “Honeywell 1226-9001”

Your email address will not be published. Required fields are marked *