Product Short Description

Basic Identification

  • Brand: HIMA Paul Hildebrandt GmbH (Germany Functional Safety OEM)
  • Full Model: H4135A
  • Product Name: SIL 3 Quad-Channel Safety Relay Output Module
  • Product Series: HIMatrix Modular Functional Safety Instrumented System

Description

Product Overview

DIN rail mount four-channel redundant safety relay module certified for SIL 3 functional safety instrumented systems (SIS). Provides fault-tolerant discrete safety switching for emergency shutdown valves, fire & gas detection interlocks, and machine safety emergency stop circuits in hazardous industrial process environments.

Technical Specifications

  • Independent Safety Relay Channels: 4 redundant Form C changeover contact channels
  • SIL Functional Safety Rating: SIL 3 (IEC 61508 / IEC 61511 certified TÜV Rheinland)
  • Single Channel Resistive Switch Capacity: 5 A @ 230 VAC; 5 A @ 24 VDC
  • Single Channel Inductive Switch Capacity: 3 A @ 230 VAC; 2 A @ 24 VDC
  • Module Supply Operating Voltage: 24 VDC, tolerance range 20–30 VDC
  • Module Static Power Consumption: 12 W maximum all channels energized
  • Safe Failure Fraction SFF: >99% diagnostic coverage rate
  • MTTFd Mean Time To Dangerous Failure: >100 years
  • Safety Response Latency: <20 ms full-channel safety trip actuation
  • Operating Temperature Range: -20 °C to +60 °C
  • Storage Temperature Range: -40 °C to +85 °C
  • Physical Dimension (W×H×D): 12.5 mm × 100 mm × 110 mm
  • Mounting Standard: 35 mm EN60715 DIN rail
  • Compliance Certifications: CE, UL, cUL, TÜV SIL 3, ATEX Zone 2/22 hazardous area compatible

Material Composition

  • Module Housing: Self-extinguishing polycarbonate UL94-V0 flame retardant plastic
  • Safety Relay Contact Material: Silver cadmium oxide anti-weld anti-arc alloy
  • Internal Safety Circuit PCB: High isolation FR4 laminate with reinforced galvanic isolation barriers
  • DIN Rail Locking Mechanism: Glass-filled polyamide impact-resistant polymer
  • Terminal Screws: Stainless steel anti-corrosion fasteners with tin-plated copper contact lugs

Structural Characteristics

  • Ultra-narrow 12.5 mm single-width DIN rail module form factor for high-density safety cabinet layout
  • Four fully electrically independent relay channels with cross-channel fault diagnostic interlock logic
  • Front panel dual bi-color LED indicators per channel: green healthy state / red fault trip state
  • Lockable screw terminal blocks preventing accidental wiring disconnection under cabinet vibration
  • Internal cross-monitoring circuit continuously compares all four relay channel states to detect single-point component faults

Working Principle

Dual redundant safety processor cores monitor four independent electromagnetic safety relay channels in a 1oo4D fault-tolerant voting architecture. All four relay contact states are continuously cross-compared via internal diagnostic logic; any single channel deviation triggers an immediate full-module safety trip and locks all output contacts into safe de-energized state. Reinforced galvanic isolation separates the low-voltage safety logic bus and high-power field safety load circuits, preventing hazardous fault propagation from field wiring back into the central safety controller rack.

Function & Feature Highlights

  1. Quad-channel redundant safety voting architecture eliminating single-point failure risk for SIL 3 safety loops
  2. Continuous cross-channel diagnostic monitoring with >99% fault detection coverage rate
  3. Mechanical contact wear counter integrated for predictive maintenance scheduling of high-cycle safety interlocks
  4. Hot-swappable DIN rail module replacement without full safety system shutdown
  5. ATEX certified for installation within Zone 2 / Zone 22 hazardous classified process cabinets
  6. Hardwired safety trip override circuit meeting IEC 61511 process safety standard requirements

Core Advantages

  • TÜV independent SIL 3 third-party certification mandatory for petrochemical, chemical, and nuclear SIS safety loops
  • Ultra-narrow single-width DIN rail footprint maximizes safety cabinet component density
  • Cross-channel fault detection prevents silent dangerous relay contact weld failures
  • Wide -20 °C to +60 °C operating temperature range compatible with unheated outdoor hazardous area enclosures
  • Long MTTFd >100-year service life minimizes safety system replacement maintenance cycles

Applicable Industries

Oil & gas upstream/downstream emergency shutdown (ESD) systems, chemical plant fire & gas safety interlock systems, power generation turbine protection safety circuits, pharmaceutical batch process hazard interlocks, refinery flare safety valve control, hazardous zone machine tool emergency stop safety systems

Installation Requirements

  1. Horizontal DIN rail mounting only; vertical orientation reduces heat dissipation and accelerates relay contact fatigue
  2. Minimum 5 mm horizontal gap between adjacent safety modules for convection cooling airflow
  3. Safety field wiring must use shielded twisted pair cable routed separately from non-safety control wiring
  4. All field safety loads require parallel transient suppression components for inductive valve actuator coils
  5. Cabinet enclosure must maintain non-condensing humidity <90% to preserve isolation barrier integrity

Usage Precautions

  1. Never parallel multiple H4135A output channels for increased switching current; contact parallelism voids SIL 3 safety certification
  2. Operating temperature exceeding +60 °C reduces MTTFd and diagnostic coverage performance below SIL 3 compliance thresholds
  3. Physical shock impact exceeding 25 G causes internal relay contact misalignment and permanent safety function degradation
  4. Annual full safety loop proof-test mandatory per IEC 61511 process safety regulation
  5. Module cannot be modified with external wiring jumpers; hardware alteration invalidates TÜV SIL certification

Reviews

There are no reviews yet.

Be the first to review “HIMA H4135A”

Your email address will not be published. Required fields are marked *

View Related Products