Product Short Description
Product Overview
The P0916AG is a 4-channel analog input termination assembly for the Foxboro I/A Series FBM204 fieldbus module. It provides field wiring interface and signal conditioning for 4-20mA analog input signals, enabling quick and reliable connection between field transmitters and the FBM module. The product features channel isolation and compact design, ideal for distributed control system I/O integration.
Description
Technical Specifications
- Number of channels: 4 analog input channels
- Supported signal: 4-20 mA current loop
- Compatible module: FBM204 Fieldbus Module
- Termination type: Compression screw terminals
- Operating temperature: -40°C to +70°C
- Storage temperature: -40°C to +85°C
- Relative humidity: 5% to 95%
- Dimensions: 4.7 × 3.0 × 10.0 inches
- Supply voltage: 24 V DC
Functional Features
- Channel-to-channel isolation prevents signal crosstalk
- Screw compression terminals ensure secure wiring connection
- Hot-swap compatible with FBM204 module
- Standardized wiring interface reduces installation time
- Compatible with DeltaV Flex.CONNECT migration solutions
Application Scenarios
- Process control system analog signal termination
- Transmitter signal interface in DCS cabinets
- Industrial automation system I/O integration
- Oil, gas and chemical process monitoring
- Power plant instrumentation signal connection
Material & Structure
- Housing: Polyamide / PVC structural casing
- Terminals: Nickel-plated copper screw terminals
- Internal circuit: Signal conditioning and protection components
- Mounting: Standard DIN rail mounting
Working Principle
The termination assembly serves as the physical interface between field instrument wiring and the FBM module. It provides surge protection and signal filtering for incoming analog signals, then routes the conditioned signals to the corresponding FBM input channels through internal wiring.
Installation Requirements
- Mount on standard 35mm DIN rail
- Use shielded twisted pair cables for analog signals
- Ground the cable shield at one end only
- Ensure correct wiring polarity for each channel
- Label each channel for easy identification and maintenance
Usage Notes
- Verify signal range matches the module configuration
- Tighten terminals properly to avoid signal loss
- Do not apply voltage exceeding the rated range
- Inspect terminals periodically for oxidation or loosening
- Use appropriate surge protection for outdoor field wiring






Reviews