Working Principle: Uses LVDT differential transformer displacement sensing. The card performs internal signal demodulation, calculation, and threshold judgement, then outputs signals to PLC/ETS through three channels: 4–20 mA analog, alarm dry contact, and backplane digital bus.
-
Technical Specifications:
-
Power Supply: 24 VDC ±10% (backplane), power consumption ≤ 5 W
-
Channel 2: Dedicated to turbine cylinder block thermal expansion
-
Channel 1: Main steam valve LVDT position
-
Measurement Bandwidth: 0–100 Hz (static)
-
Alarm Delay: 0–5 s, software adjustable
-
Hysteresis: 0–20% FS
-
Signal Output:
-
4–20 mA analog (independently isolated per channel)
-
Relay dry contact (with A6740 relay card)
-
System bus communication (Modbus/Ethernet via A6560R processor)
-
Protection Logic: Triggers alarm on single-side over-expansion; sends hard-contact trip signal to PLC/ETS on differential over-limit or jam, participating in load reduction and shutdown interlock.
-
Application: Steam turbine cylinder expansion monitoring during startup, shutdown, and thermal transient.
-
Installation Requirements: Install PR9350 series LVDT probes in pairs at the axial support sliders of left/right cylinder blocks.
-
Usage Notes: Must use inductive LVDT half-bridge/full-bridge sensors only; do not substitute other transducer types.