Product Short Description
Product Introduction:
The Emerson 1410S2AA32AD4N7RD is a head-mountable temperature transmitter that accepts RTD (Pt100) input and provides a 4–20 mA HART output. It is designed for direct sensor head mounting in pipe, vessel, or duct applications where space is limited. The transmitter features HART 7 communication for remote configuration and diagnostics.
Description
Technical Specifications:
- Part Number: 1410S2AA32AD4N7RD
- Input Type: Pt100 RTD, 2-wire (per model suffix “S2”)
- Temperature Range: -200°C to +650°C (-328°F to +1202°F)
- Output: 4–20 mA, HART 7 protocol
- Accuracy: ±0.1°C (±0.18°F) at 0°C
- Supply Voltage: 12–42 VDC (loop-powered)
- Process Connection: 1/2″ NPT male (integral)
- Enclosure Rating: NEMA 4X / IP66 / IP67
- Housing Material: 316L Stainless Steel
- Electrical Connection: 1/2″ NPT conduit entry with PG9 cable gland
- Ambient Temperature: -40°C to +85°C (-40°F to +185°F)
- Response Time (T63): < 5 seconds (in thermowell)
- Dimensions: 108 mm × 57 mm × 57 mm (L × W × D)
- Weight: 0.6 kg (1.3 lb)
Functional Features:
- HART 7 communication for remote configuration via handheld or DCS
- Two-wire loop power — no separate power supply needed
- Sensor fault detection (open circuit, short circuit, out-of-range)
- Programmable damping: 0.5–32 seconds
- Reverse polarity protection
Performance Parameters:
- Linearity: ±0.05% of span
- Hysteresis: ±0.03% of span
- Long-Term Drift: ±0.05% of span per year
- Input Impedance (RTD): 100 Ω (2-wire)
- Output Load: 200–1200 Ω
Structural Features:
- Compact 316L stainless steel housing
- 1/2″ NPT process connection (bottom-mounted)
- PG9 cable gland with O-ring seal
- 4-button HART interface on top (or via HART communicator)
- DIN rail clip optional (separate accessory)
Working Principle:
The transmitter applies a precise excitation current to the Pt100 RTD and measures the resulting voltage drop. The resistance is converted to temperature using the Callendar-Van Dusen equation. The microprocessor linearizes the signal, applies damping, and outputs a 4–20 mA signal proportional to temperature. HART communication superimposes digital data on the 4–20 mA signal.
Key Advantages:
- ±0.1°C accuracy without field calibration
- HART 7 enables remote diagnostics — reduces site visits
- NEMA 4X / IP67 rating for harsh environments
- 2-wire RTD simplifies wiring in existing installations
Applicable Industries: Oil and gas, power generation, chemical processing, food and beverage, pharmaceutical, water treatment
Installation Requirements:
- Mount in thermowell with immersion depth ≥ 10× sheath diameter
- Use 3-wire or 4-wire RTD for best accuracy (2-wire has lead resistance error)
- Loop resistance: 200–1200 Ω at 24 VDC
- Torque process connection to 30 N·m
Usage Notes:
- Perform HART configuration using Rosemount 475 Field Communicator or AMS Suite
- Recalibrate every 2 years or per SIL requirement
- Do not exceed 42 VDC supply voltage
- Replace O-ring on cable gland annually in corrosive service





-500x500.jpg)