Product Short Description

Product Name KT Series 3-Pole Thermal-Magnetic Trip Unit

Product Introduction The Eaton KT3315TA is a 3-pole adjustable thermal-magnetic trip unit engineered for Eaton K-frame Series C molded case circuit breakers. It delivers precise overcurrent and short-circuit protection with configurable current thresholds for industrial power distribution systems.

Description

Technical Specifications

  • Nominal Rated Current: 315A
  • Adjustable Thermal Range: 250A to 315A
  • Adjustable Magnetic Range: 1575A to 3150A
  • Maximum Voltage Rating: 600V AC
  • Number of Poles: 3 poles
  • Trip Type: Adjustable thermal, adjustable magnetic
  • Compatibility: Eaton K-frame Series C molded case circuit breakers
  • Operating Temperature Range: -40°C to +85°C

Functional Features

  • Front-facing adjustment dials enable simple current calibration without disassembly
  • Precision bimetallic thermal element provides time-delayed overload protection
  • High-sensitivity magnetic trip mechanism delivers instantaneous short-circuit response
  • Compact form factor integrates directly with compatible circuit breaker frames
  • Calibrated at the factory for consistent performance across operating conditions

Application Scenarios

  • Industrial power distribution panels and switchgear assemblies
  • Motor control centers and motor branch circuit protection
  • Commercial facility electrical infrastructure
  • Manufacturing plant process power systems
  • Renewable energy power distribution systems

Material & Construction

  • High-temperature thermoplastic housing for electrical insulation and mechanical durability
  • Silver alloy internal conductive components for stable electrical performance
  • Precision-calibrated bimetallic strips for accurate thermal trip response
  • Wound magnetic coils for reliable short-circuit detection

Operating Principle

  • Thermal protection operates via bimetallic strips that deflect under sustained overload current, releasing the circuit breaker trip latch after a calibrated time delay.
  • Magnetic protection operates via solenoid coils that generate sufficient magnetic force to actuate the trip mechanism instantaneously during short-circuit fault conditions.

Installation Requirements

  • Install exclusively into compatible Eaton K-frame Series C molded case circuit breakers
  • Perform installation and adjustment by qualified electrical personnel
  • Apply specified torque values to all terminal connections
  • Verify compatibility with specific circuit breaker catalog numbers before commissioning

Certifications UL Listed, CSA Certified, IEC compliant