Product Short Description

Product Name: Eaton CE15KN3 (CE15KN3AB) Freedom Series IEC Non-Reversing Magnetic Contactor.
Product Overview: A 3-pole, non-reversing IEC contactor from Eaton’s Cutler-Hammer Freedom K-Frame series. It is designed for switching medium-power 3-phase AC motors and industrial loads. The CE15KN3 designation commonly corresponds to the CE15KN3AB complete part number.

Description

Technical Specifications:
  • Frame Size: K (65 mm frame)
  • Poles: 3 (normally open contacts)
  • Continuous Current Rating: 73 A (UL), 80 A (IEC thermal current)
  • Maximum Voltage: 600 V AC
  • Coil Voltage: 110 VAC at 50 Hz / 120 VAC at 60 Hz (CE15KN3AB variant); alternative variants available at 440–480 VAC coil
  • Motor Ratings:
    • 5 HP at 115 V 1-phase
    • 10 HP at 230 V 1-phase
    • 20 HP at 200 V 3-phase
    • 25 HP at 230 V 3-phase
    • 50 HP at 460/575 V 3-phase
  • Coil Inrush Power: 80–100 VA; Sealing Power: 9–12 VA
  • Mounting: Steel mounting plate or 35 mm DIN rail
  • Wire Size: Main #10–#8 AWG; Control #12–#14 AWG
  • Torque: Main 15 N·m; Control 7 N·m
  • Operating Temperature: –25°C to +70°C
  • Protection Rating: IP00 (open type)
  • Dimensions: Approx. 151 × 182 × 104 mm
  • Weight: Approx. 4.1 kg
  • Certifications: UL, CSA, IEC 947-4-1, DIN VDE 0600
Functional Features:
  • Reliable switching of medium to large 3-phase AC loads
  • Silver-cadmium oxide contacts with high conductivity and arc-erosion resistance
  • Mechanical life: 20,000,000 operations; Electrical life: 2,000,000 operations
  • Compatible with auxiliary contact modules for control circuit expansion
  • Open-type construction for optimal heat dissipation in enclosed panels
Working Principle: When the coil is energized at the rated control voltage, an electromagnetic field attracts the moving armature,
closing the three main contacts to complete the 3-phase load circuit. De-energizing the coil releases the armature, opening the contacts
and disconnecting the load.
Application Scenarios: Full-voltage starting of 3-phase induction motors (fans, pumps, compressors), main load switching in control
panels, motor control centers (MCC), and industrial power distribution.
Installation & Usage Notes:
  • Verify coil voltage matches the available control power (110–120 VAC for CE15KN3AB; 440–480 VAC for CE15KN3CB)
  • Mount securely on steel plate or DIN rail inside an enclosed panel; observe IP00 open-type rating — fingers and tools must not contact
    live parts
  • Use correct wire gauges and torque values to prevent overheating at terminals
  • Ensure adequate spacing around the contactor for heat dissipation
  • Pair with appropriately sized overload relays for motor protection
  • Do not exceed 73 A continuous current or the listed HP ratings per IEC AC-3 utilization category
  • Maintain control voltage within 85–110% of nominal during pull-in; release occurs at 20–75% of nominal