Product Short Description
Product Name: Generator Load Sharing and Frequency Control Unit
Product Introduction: LSU-112DG is a generator load sharing controller from DEIF Uni-Line series, designed for diesel and gas generator sets. It controls prime mover speed to realize frequency regulation and active power load sharing between parallel generators.
Description
Technical Specifications:
- Power Supply: 18 ~ 35 VDC
- Frequency Measurement Range: 40 ~ 70 Hz
- Voltage Measurement Range: 57.7 ~ 690 VAC
- Mounting Type: 35 mm DIN rail or base mounting
- Protection Grade: IP40 (front panel)
- Operating Temperature: -25 ℃ ~ +70 ℃
- Output Contacts: 2 relay outputs for speed control, 8A / 3A rating
- Compliance: DNV-GL, ABS, IEC 60945, ISO 8528
Function Features: Built-in power and frequency transducer, isochronous operation mode and constant power mode, relay pulse output for mechanical governor, LED status indicators, multi-generator parallel load sharing, adjustable deadband and gain parameters.
Application Scenarios: Marine power plants, island multi-generator parallel systems, industrial captive power stations, biomass cogeneration plants, emergency backup power systems.
Material Composition: Plastic DIN rail housing, microprocessor control chip, voltage and current sampling circuit, relay contact module, LED indicator, terminal block.
Structural Features: Standard 35 mm DIN rail modular housing, screw terminal connection, front panel status LED indicators and adjustment potentiometers, compact design for control cabinet installation.
Working Principle: Samples generator output voltage and current, calculates real-time frequency and active power, outputs speed increase/decrease pulse signals to the governor actuator, adjusts engine speed to realize frequency stability and load equalization.
Installation Requirements: Install inside control cabinet on standard DIN rail; connect voltage transformer and current transformer signals correctly; wire governor actuator according to terminal diagram.
Usage Notes: Calibrate CT and VT sampling signals before commissioning; set load sharing parameters according to generator capacity ratio; verify relay output polarity before connecting to governor; perform parallel operation test step by step.