Description
Technical Specifications
2 analog outputs
Voltage output ±10 V
Current output 0–20 mA / 4–20 mA
Voltage resolution ±12 bit
Current resolution 12 bit
Conversion time 200 µs
Settling time 1 ms
Bus power 0.01 W
Internal I/O power 1.1 W
Protection rating IP20
Horizontal operation -25 to 60 °C
Vertical operation -25 to 50 °C
Functional Features
Voltage / current selection by terminal wiring
Short-circuit-protected outputs
Internal enable relay
First-order output filter 10 kHz
LED diagnostics
Channel-to-bus isolation
Application Scenarios
Process control
Valve and actuator command
Variable-speed drive setpoint
Test benches
Packaging and machine automation
Material / Structure
X20 modular I/O housing
12.5 mm pitch mechanical format
Separate terminal block
Bus base module required
Operating Principle
The module converts a digital process value from the X20 bus into a calibrated analog voltage or current output that drives field actuators.
Installation Requirements
Install on X20 bus base module
Order X20BM11 bus module separately
Order X20TB06 / X20TB12 terminal block separately
Mount on DIN rail inside control cabinet
Usage Notes
Respect minimum and maximum load impedance
Voltage output typically requires ≥ 1 kΩ load
Current output typically requires ≤ 600 Ω load
Do not assume channel-to-channel isolation
Configure signal range in Automation Studio





Reviews