Product Short Description

Product Series: B&R 5P Series Industrial Power Unit

Product Brief: Regulated DC power supply module designed for B&R distributed automation control systems. It converts input AC power into stable DC power to supply power for PLC, I/O modules, human-machine interfaces and other on-site control components, serving as the core power distribution unit of industrial control cabinets.

Description

Technical Specifications
  • Input Voltage: 100 ~ 240 V AC, 50/60 Hz
  • Output Voltage: 24 V DC
  • Rated Output Current: 10 A
  • Operating Temperature: -20 °C ~ +70 °C
  • Storage Temperature: -40 °C ~ +85 °C
  • Relative Humidity: 5% ~ 95% RH (Non-condensing)
  • Efficiency: ≥ 92%
  • Isolation Voltage: 3000 V AC
Functional Features
  1. Wide-range AC input, automatic adaptation to global industrial power grids
  2. Constant voltage output with over-voltage, over-current and short-circuit protection
  3. Active power factor correction to reduce grid harmonic interference
  4. Built-in surge suppression circuit to resist instantaneous voltage spike
  5. Power status LED indication and remote fault signal output
  6. Parallel operation support for capacity expansion
Performance Parameters
  • Total Output Power: 240 W
  • Output Voltage Ripple: ≤ 120 mVpp
  • Vibration Resistance: 10 Hz ~ 180 Hz, 1 g continuous vibration
  • Shock Resistance: 20 g peak acceleration (10 ms duration)
  • MTBF: ≥ 120000 hours
Material Composition
  • Main Circuit Board: FR-4 high-temperature flame-retardant multilayer PCB
  • Enclosure: Die-cast aluminum alloy shell with electrophoretic coating
  • Core Components: High-frequency switching power tubes, rectifier bridges, electrolytic capacitors, inductors
  • Terminal Blocks: Copper alloy silver-plated contacts with reinforced plastic base
  • Heat Dissipation Components: Aluminum heat sink and thermal conductive silicone pads
Structural Characteristics
  • Standard 35 mm DIN rail mounting structure
  • Integrated ventilation grille on shell for natural convection heat dissipation
  • Front panel equipped with power indicator, fault indicator and output terminals
  • Internal modular circuit layout, separated AC input area and DC output area
  • Left and right locking buckles for combined installation with adjacent modules
Working Principle

AC input power passes through EMI filter, rectifier and PFC circuit to complete preliminary power conditioning. The high-frequency switching circuit converts intermediate DC voltage into high-frequency AC, which is isolated and stepped down by high-frequency transformer. After rectification and filtering, stable 24 V DC power is output to load equipment. The built-in sampling circuit monitors output parameters in real time and triggers protection actions once abnormal states occur.

Advantages & Highlights
  1. Ultra-high conversion efficiency, low heat generation during long-term operation
  2. Complete multi-level protection mechanism to guarantee load equipment safety
  3. Excellent electromagnetic compatibility, no interference to surrounding control modules
  4. Wide input voltage range, stable operation under unstable grid conditions
  5. Metal shell structure with outstanding mechanical strength and heat dissipation performance
Applicable Industries

General machinery manufacturing, packaging equipment, textile industry, water treatment, new energy, logistics automation, petrochemical industry

Installation Requirements
  1. Mount firmly on standard 35 mm DIN rail inside sealed industrial control cabinet
  2. Maintain ≥ 25 mm clearance around the module to ensure unobstructed air circulation
  3. Use cables with matching current rating for AC input and DC output wiring
  4. Implement reliable protective grounding in accordance with industrial electrical standards
  5. Install away from heat sources and high-power frequency conversion equipment
Usage Notes
  1. Cut off input power before wiring, disassembly and routine maintenance
  2. Do not operate under continuous full-load overload conditions
  3. Clean dust on ventilation grilles every 3 months to avoid heat accumulation
  4. Prohibit disassembly of sealed internal structure without official authorization
  5. Prevent liquid splash and corrosive gas from contacting the module surface