Product Short Description

Product Name: 16-Channel 2-Wire HART Analog Input Terminal Block, Series 2 Plus

Product Introduction: High-density analog input termination unit matched with DeltaV 16-channel 4–20mA analog input card. Designed for 2-wire HART transmitters, used to terminate field analog signals and connect to DeltaV I/O carrier.

Description

Technical Specifications
  • Channel Quantity: 16 independent analog input channels
  • Supported Signal: 4–20mA DC, 2-wire transmitter, HART 5 / HART 7 protocol compatible
  • Transmitter Supply Voltage: Minimum 13.5 VDC @ 20mA
  • Over-range Detection Range: 2–22mA
  • Isolation: Channel-to-bus optical isolation, 1000 VDC withstand voltage
  • Power Consumption: Simplex 85mA typical, 150mA maximum; Redundant 110mA typical, 200mA maximum
  • Operating Temperature: -40°C ~ +70°C
  • Storage Temperature: -40°C ~ +85°C
  • Relative Humidity: 5% ~ 95%, non-condensing
  • Protection Class: IP20

    Function Features

  • Built-in HART signal modulation and demodulation circuit
  • Channel open-circuit, short-circuit fault diagnosis
  • Hot-swappable supporting online replacement without system shutdown
  • Keyed mechanical anti-misplug design to prevent mismatched I/O cards
  • Conformal coating against corrosive industrial atmosphere, compliant with ISA-S71.04 Class G3

    Working Principle: Receive continuous analog current signals from field transmitters, filter interference signals, transmit conditioned signals to paired analog input card; realize bidirectional HART digital signal transmission for smart instrument parameter configuration.

    Material & Structure

  • Housing Material: Flame-retardant reinforced engineering plastic
  • Internal Circuit Board: FR4 printed circuit board with conformal coating
  • Structure: Integrated rectangular module, front panel status indicator LED, rear interlocking connector for I/O carrier

    Installation Requirements

  • Mount vertically on DeltaV standard I/O carrier
  • Maintain 20mm minimum ventilation gap between adjacent modules
  • Field wiring uses screw terminal connections, torque 0.8–1.2 N·m
  • Ground shielding wire connected to cabinet protective ground point

    Application Scenarios: Oil & gas plant, chemical processing, power generation, water treatment, pharmaceutical manufacturing; collecting pressure, temperature, flow, liquid level analog signals.

    Usage Notes

  • Static sensitive device, anti-static wrist strap required during handling
  • Do not disassemble the module housing; no user-serviceable internal components
  • Avoid wiring live field circuits during module hot swap
  • Regularly inspect terminal screw tightening status to prevent loose contact