Product Short Description

Product Name: Generator Load Sharing and Frequency Control Unit

Product Introduction: LSU-112DG is a generator load sharing controller from DEIF Uni-Line series, designed for diesel and gas generator sets. It controls prime mover speed to realize frequency regulation and active power load sharing between parallel generators.

Description

Technical Specifications:

  • Power Supply: 18 ~ 35 VDC
  • Frequency Measurement Range: 40 ~ 70 Hz
  • Voltage Measurement Range: 57.7 ~ 690 VAC
  • Mounting Type: 35 mm DIN rail or base mounting
  • Protection Grade: IP40 (front panel)
  • Operating Temperature: -25 ℃ ~ +70 ℃
  • Output Contacts: 2 relay outputs for speed control, 8A / 3A rating
  • Compliance: DNV-GL, ABS, IEC 60945, ISO 8528

Function Features: Built-in power and frequency transducer, isochronous operation mode and constant power mode, relay pulse output for mechanical governor, LED status indicators, multi-generator parallel load sharing, adjustable deadband and gain parameters.

Application Scenarios: Marine power plants, island multi-generator parallel systems, industrial captive power stations, biomass cogeneration plants, emergency backup power systems.

Material Composition: Plastic DIN rail housing, microprocessor control chip, voltage and current sampling circuit, relay contact module, LED indicator, terminal block.

Structural Features: Standard 35 mm DIN rail modular housing, screw terminal connection, front panel status LED indicators and adjustment potentiometers, compact design for control cabinet installation.

Working Principle: Samples generator output voltage and current, calculates real-time frequency and active power, outputs speed increase/decrease pulse signals to the governor actuator, adjusts engine speed to realize frequency stability and load equalization.

Installation Requirements: Install inside control cabinet on standard DIN rail; connect voltage transformer and current transformer signals correctly; wire governor actuator according to terminal diagram.

Usage Notes: Calibrate CT and VT sampling signals before commissioning; set load sharing parameters according to generator capacity ratio; verify relay output polarity before connecting to governor; perform parallel operation test step by step.