Description
- Dimensions: 90 mm (A) x 50 mm (B) x 100.5 mm (C) (J large Type)
- Standard Coil Voltages: 24, 48, 72, 110, 125, 220 VDC; 63.5, 110, 127, 230 VAC (50-60 Hz)
- Voltage Range: +10% to -20% of nominal voltage (UN)
- Average Consumption (change-over): 45 W
- Pick-up Time: < 10 ms (VDC), < 20 ms (VAC)
- Contact Material: AgNi (Silver-Nickel)
- Contact Distance: 1.8 mm
- Permanent Current: 10 A
- Instantaneous Current: 80 A during 200 ms / 200 A during 10 ms
- Max. Making Capacity: 40 A / 0.5 s / 110 VDC
- Max. Opened Contact Voltage: 250 VDC / 400 VAC
- Mechanical Endurance: 10^7 operations
- Operating Temperature: -40 °C to +70 °C
- Storage Temperature: -40 °C to +85 °C
- Max. Operating Humidity: 93% at +40 °C
- Operating Altitude: < 2000 m
- Reset: Manual reset
- Application: Tripping and locking applications in power systems requiring high quality operating time and breaking capacity