Interface: RS-422 / RS-485
-
Connection Method:
-
Communication Function: Half-duplex
-
Synchronization Method: Start-stop synchronization
-
Transmission Speed: 1200 / 2400 / 4800 / 9600 / 19200 / 38400 bps
-
Transmission Code: ASCII / binary
-
Character Length: 7 / 8 bits
-
Stop Bit Length: 1 / 2 bits
-
Parity Check: None / even / odd
-
Lag Time After Data Transmission: 1 ms (lag time to start receiving data again after data transmission)
-
Transmission Distance:
-
Number of Ports: 2 ports
-
I/O Wiring: AKB131, AKB132, AKB133, AKB134 cables, etc. (3-pair shielded cable: AKB161 or AKB162)
-
Wiring Connection: D-sub 9-pin (female × 2) clamped with terminal block’s M4 screws (5 poles × 2)
-
Current Consumption: 0.5 A
-
Weight: 0.3 kg
-
Suffix Code Specifications:
-
S: Standard Type
-
0: Basic Type
-
5: With no explosion protection
-
E: With explosion protection
-
1: With ISA Standard G3 option
-
Compatible Mounting Units: Field control units (AFV10, AFV30, AFV40, AFF50), ESB bus node unit (ANB10), optical ESB bus node unit (ANB11), ER bus node unit (ANR10).
-
Application Scenarios: Serial communication between Yokogawa DCS and external subsystems such as PLCs, sequencers, FA-M3 controllers, and third-party automation devices in industrial process control, power systems, and environmental monitoring.
-
Installation Requirements: Mount on compatible ANB10, ANR10, AFF50, AFV10, AFV30, or AFV40 units. Use specified Yokogawa I/O wiring cables (AKB131, AKB132, AKB133, AKB134 or AKB161/AKB162 3-pair shielded cable).
-
Usage Notes: Transmission speed selection depends on communication function, subsystems, and connection method. Maintain specified transmission distance limits (15 m for RS-422, 1200 m for RS-485). Ensure proper wiring connections using D-sub 9-pin female connectors or M4 screw terminal blocks.
Reviews