Product Short Description
Product Brief Introduction
High-density 8-channel HART-capable analog input terminal block for large-scale analog transmitter signal collection, optimized for mass temperature, pressure, flow measurement loops in large process plants, each channel fully isolated with independent HART communication processing circuit.
Description
Technical Specifications
- Channel Count: 8 fully isolated 4–20mA analog input channels
- HART Support: Independent HART modulation/demodulation circuit per channel, simultaneous multi-channel HART communication without signal conflict
- Loop Power Supply: 24 VDC loop power output to 2-wire field transmitters
- Isolation Voltage: 1500 VAC channel-to-backplane isolation
- Maximum Field Cable Length: 1000 meters shielded twisted pair cable per channel
Material & Structural Design
High-density compact layout to save chassis slot space, integrated wire strain relief guides, dual-layer EMI shielding PCB, front panel per-channel fault LED alarm indicators.
Working Principle
Each channel contains independent surge suppression, optocoupler isolation and HART signal separation circuits; analog 4–20mA measurement signals and HART digital diagnostic data are separately transmitted to paired DeltaV high-density AI function cards, supporting simultaneous multi-transmitter asset management diagnostics via AMS software.
Application Scenarios
- Large chemical complex, power station, pulp & paper mill mass analog measurement signal cabinets
- Multi-point temperature monitoring storage silos, pipeline flow metering stations
Installation Requirements
All field instrument cables must use shielded twisted pair wiring; cable shield grounding point concentrated at control cabinet internal terminal bar only, no multiple grounding points to eliminate ground loop noise