Product Short Description

Product Introduction

16-channel high-density analog input card for DeltaV distributed control systems, optimized for large-scale multi-transmitter field signal acquisition. Captures 4–20 mA analog measurement signals with full HART bidirectional communication support, delivering maximum rack density for large process plant DCS installations.

Description

Technical & Electrical Specifications

  • Module Supply Input: 24 V DC ±10% rack backplane power
  • Field Circuit Rating Per Channel: Uo=28.7 V, Io=33 mA, Po=607 mW
  • Total Independent Input Channels: 16 galvanically isolated channels
  • Supported Field Signal: 4 mA ~ 20 mA 2-wire SMART transmitter loop signals
  • HART Protocol Support: HART 5, HART 6, HART 7 bidirectional transparent transmission
  • Intrinsic Safety Rating: Ex nA nL IIC T4 Gc for Division 2 hazardous zone cabinet installation
  • Channel Fault Detection: Open wire, short circuit, over-range / under-range signal alarm

Mechanical & Material Specifications

  • Mounting Format: DeltaV S-Series rack backplane slot plug-in module
  • Housing Material: Black flame-retardant ABS industrial plastic
  • Required Matching Accessory: Dedicated 16-channel terminal base assembly

Environmental Parameters

  • Operating Temperature Band: -40 °C ~ +75 °C
  • Storage Temperature Range: -55 °C ~ +85 °C
  • Humidity Operation Limit: 5% ~ 95% RH, no condensation

Function Features

  1. 16 high-density isolated analog input channels maximizes rack signal acquisition capacity
  2. Full HART multi-drop communication compatibility for multi-transmitter field loops
  3. Hot-swappable hardware design for online maintenance without DCS system shutdown
  4. Per-channel independent fault diagnostic with dedicated backplane alarm reporting
  5. High-speed backplane digital bus with deterministic 100 ms maximum channel refresh rate
  6. Energy-limited Ex certified field circuits for hazardous industrial cabinet deployment

Working Principle

Sixteen individual isolated current sampling circuits convert field 4–20 mA analog signals to high-resolution digital measurement data. Integrated multi-channel HART modem extracts digital configuration and diagnostic data superimposed on analog current waveforms. Onboard module processor aggregates all channel data and transmits via high-speed DeltaV backplane serial bus to primary system controller for process control calculation and HART device data access.

Advantage Highlights

  1. 16-channel density reduces required rack quantity by 50% versus 8-channel equivalent input modules
  2. Multi-drop HART support reduces field cable count for multi-transmitter instrument loops
  3. Hot-swap design minimizes process downtime during I/O hardware maintenance
  4. Wide extreme temperature operating range suitable for outdoor remote process control cabinets
  5. Ex nA IIC T4 certification compatible with all Class I Division 2 hazardous industrial locations
  6. Per-channel independent isolation eliminates cross-channel measurement interference

Applicable Industries

Large-scale petrochemical complex control, natural gas transmission pipeline monitoring, coal-fired power plant DCS, municipal water/wastewater large treatment facilities, bulk pharmaceutical continuous manufacturing

Installation Requirements

  1. Insert module only into matching DeltaV S-Series I/O rack backplane expansion slots
  2. Install matching model dedicated 16-channel terminal base unit prior to module insertion
  3. Separate field instrument wiring and rack power wiring with physical cable barrier partitions
  4. Rack cooling airflow must maintain chassis internal temperature below 75 °C maximum

Usage Precautions

  1. Do not connect field devices exceeding maximum 33 mA channel current limit
  2. All field wiring within hazardous Division 2 cabinets must comply with Emerson Ex installation specifications
  3. Disconnect field terminal wiring before executing hot-swap module replacement
  4. Avoid rack placement adjacent to unshielded high-frequency motor drive power equipment
  5. Replace only with factory-original KJ3223X1-BA1 modules; third-party substitutes prohibited
  6. Perform semi-annual full channel HART communication diagnostic testing