Product Short Description

Basic Product Identification

  • Manufacturer: Metso Outotec (Metso Automation Division)
  • Full Model Code: IOP371
  • Product Category: DCS I/O Bus Fiber/Twisted Pair Extender Module
  • Product Series: Metso DNA Distributed Control System Series

Description

Product Overview

This module is dedicated bus extension hardware for Metso DNA DCS platform, realizing long-distance transmission of proprietary DCS I/O backplane bus signals between central control rack and remote field I/O racks, breaking the 30 m limit of standard DCS backplane wiring distance, supporting multi-node remote I/O rack cascading, maintaining complete real-time signal synchronization and data integrity in mineral processing, metallurgy long workshop control environments.

Technical Core Specifications

  1. Bus Communication Parameters
    • Native bus protocol: Metso DNA proprietary I/O backplane bus
    • Communication baud rate: 1 Mbps ~ 10 Mbps automatic adaptive
    • Maximum extension transmission distance: 1000 m (twisted pair cable), 2000 m (single-mode optical fiber)
    • Single module expandable remote I/O rack quantity: 8–16 cascaded nodes
  2. Isolation Performance
    • Bus side and field remote side galvanic isolation voltage: 2500 Vrms
  3. Power Supply Specification
    • Power input: 24 V DC backplane bus power supply
    • Static power consumption: 5 W low energy loss design
  4. Mechanical Dimensions & Weight
    • Overall size: 120 mm (L) × 90 mm (W) × 45 mm (H)
    • Net weight: 0.2 kg
    • Mounting form: 35 mm DIN rail cabinet mounting
  5. Environmental Rating
    • Operating temperature: −20 °C ~ +70 °C
    • Relative humidity: 5%–95% non-condensing
    • Protection class: IP20

Functional Features

  1. Dual media support: twisted copper pair and single-mode fiber optical transmission interface interchangeable via pluggable interface adapter
  2. Real-time bus signal synchronization correction circuit, eliminating transmission delay deviation between multi-node remote racks
  3. Automatic bus link fault diagnosis, front panel LED indicator for link breakage, short circuit and communication timeout
  4. Built-in signal surge suppression circuit for field remote cable lightning surge protection
  5. Plug-and-play cascading without complex software address configuration, automatic node identification
  6. Bidirectional signal amplification and reshaping to eliminate long-distance cable signal attenuation distortion

Working Principle

Metso DNA central rack CPU backplane I/O bus signal enters IOP371 local bus interface, processed by signal shaping and isolation circuit, converted to differential twisted pair or optical signal for long-distance transmission to remote field IOP371 slave module. Slave module restores original DCS backplane bus signal and outputs to remote I/O rack backplane, realizing transparent bus data exchange between central control unit and remote analog/digital I/O modules without protocol conversion delay.

Material & Structural Composition

  • PCB: Miniaturized high-density FR4 circuit board with surface mount components
  • Shell: Lightweight black flame retardant PC plastic integrated enclosure
  • Transmission interface: Industrial grade fiber SC adapter and screw-type twisted pair terminal block
  • Internal core components: Bus signal isolation optocoupler, signal reshaping amplifier chip, lightning protection TVS diode array

Advantage Highlights

  1. Ultra-low power consumption reduces cabinet cooling load for long-term continuous operation
  2. Fiber transmission completely eliminates electromagnetic interference in mineral processing high-vibration, high-magnetic field workshop
  3. Plug-and-play cascading greatly shortens DCS remote I/O system construction and debugging cycle
  4. Compact small volume saves cabinet installation space compared with third-party bus repeaters
  5. Full compatibility with all Metso DNA series I/O racks without system firmware upgrade

Applicable Industries

Mining mineral flotation control, iron & steel metallurgy sintering workshop, cement raw material processing plant, non-ferrous metal smelting, aggregate crushing production line, long-distance water treatment plant distributed control

Installation Mandatory Requirements

  1. Install inside sealed control cabinet, avoid direct dust and mineral powder erosion on module surface
  2. Optical fiber cable bending radius must maintain ≥30 mm to prevent optical signal attenuation
  3. Twisted pair communication cable must use industrial shielded differential pair cable, shielding grounded at remote cabinet side only
  4. Each cascading branch total cable length cannot exceed maximum rated transmission distance of module

Operation & Maintenance Precautions

  1. Inspect optical fiber interface dust contamination every 6 months, clean only with professional fiber wiping paper
  2. Do not hot-plug twisted pair bus terminals under system running state to avoid bus communication collapse
  3. Avoid installing module near high-power frequency converters and heavy-duty motor starters without metal shielding partition
  4. Replace module when communication fault LED keeps steady bright after cable full inspection