Product Short Description

Product Brief

Rack-mounted analog output module for closed-loop process regulation, outputs standard 4–20 mA control signals to field valve positioners, variable frequency drives, no L extended shielding variant.

Technical Specifications

  • Model Series: ACN CS D2014 Analog Output Subseries

Description

  • Power Supply: 24 VDC ±10, rated power consumption 13 W
  • Analog Output Channels: 8 isolated 4–20 mA current output channels
  • Max Output Load Resistance per Channel: 1000 Ω
  • Output Signal Resolution: 16-bit DAC digital-to-analog conversion
  • Backplane Bus: Metso proprietary ACN high-speed internal bus
  • Operating Temperature Range: -20 °C ~ +60 °C
  • Storage Temperature Range: -40 °C ~ +85 °C
  • Humidity Tolerance: 5%–95% non-condensing
  • Protection Grade: IP20 module body, IP54 full rack assembly
  • Dimensions: 220 H × 160 W × 35 D mm
  • Net Weight: 0.79 kg

Functional Features

  1. 8 independent isolated 4–20 mA analog output channels with high load capacity
  2. Per-channel short-circuit automatic cut-off protection circuit
  3. Front panel independent LED channel fault indicator for overload/short-circuit
  4. Built-in output signal ramp function to avoid sudden process equipment shock
  5. Onboard Flash memory stores output curve calibration parameters
  6. Full hot-swap compatible with ACN CS rack backplane
  7. Automatic channel fault recovery after short-circuit load removal

Performance Parameters

  • Analog Output Control Accuracy: ±0.08% full scale
  • Channel Isolation Voltage: 1500 VAC output circuit to backplane bus
  • DAC Conversion Response Time: ≤ 0.8 ms per channel
  • Surge Withstand Capacity: 2 kV ESD contact discharge, 4 kV EFT
  • Vibration Resistance: 10–150 Hz, 1 g continuous operation
  • Max Control Cable Length: 180 m shielded twisted pair cable

Material Composition

  • PCB Substrate: FR4 high-Tg low-drift industrial fiberglass circuit board
  • Output Terminal Blocks: Gold-plated phosphor bronze anti-oxidation terminals
  • Reference Circuit: Ultra-low temperature drift precision metal film resistors
  • Shield Frame: Single-layer cold-rolled steel analog output signal isolation shielding
  • Mounting Housing: Black extruded aluminum alloy hard anodized anti-corrosion coating

Structural Characteristics

  • Standard 1U dual-latch plug-in rack card structure
  • Front panel 8-group independent LED overload fault indicator array
  • Rear gold finger connector docking with rack backplane bus
  • Independent wiring terminal compartment for field control signal cable access
  • Double isolation barrier separates analog output circuit and digital backplane bus circuit

Working Principle

Rack main controller transmits target setpoint data via ACN backplane bus to module internal 32-bit processing chip. Digital setpoint values convert to stable 4–20 mA analog current signals through 16-bit DAC circuits, isolated analog output circuits transmit control signals to field valve positioners and VFD equipment. Per-channel hardware monitoring circuits detect load short-circuit and overload conditions, automatically cut off channel output and trigger front panel fault LED; channel resumes normal output after load fault elimination.

Advantage Highlights

  1. High 1000 Ω load resistance compatible with long-distance field valve positioner wiring
  2. Per-channel independent short-circuit protection avoids full module shutdown under single-channel fault
  3. Built-in signal ramp function eliminates sudden process flow/pressure impact
  4. Ultra-high output stability guarantees long-term closed-loop control precision
  5. Hot-swap maintenance without full rack power shutdown
  6. Factory pre-calibrated output curves without on-site adjustment required

Applicable Industries

  • All Metso process automation closed-loop control scenarios: mining flotation valve regulation, pulp mill liquor flow control, petrochemical reactor temperature/pressure adjustment, water treatment dosing valve control, cement kiln air volume regulation

Installation Requirements

  1. Install inside standard Metso ACN CS 8/16-slot control rack
  2. Maintain 10 mm vertical ventilation gap between adjacent modules
  3. Field control signal cables adopt shielded twisted pair wiring, single-point cabinet PE grounding
  4. Cabinet PE grounding resistance ≤ 4 Ω to suppress output signal drift interference
  5. Stabilize rack backplane 24 VDC power before hot-swapping modules
  6. Control cabinet internal continuous operating temperature below 55 °C

Operation & Maintenance Precautions

  1. ESD anti-static wrist strap mandatory during module disassembly and wiring
  2. Do not connect channel output terminals to power supply circuits directly
  3. Conduct semi-annual inspection of terminal block screw tightness
  4. Separate analog output signal cables from high-power inverter wiring
  5. Spare modules stored in sealed anti-static packaging with desiccant packs
  6. Cut off field control valve wiring terminals before disassembling terminal blocks

Reviews

There are no reviews yet.

Be the first to review “Metso D201483”

Your email address will not be published. Required fields are marked *

View Related Products