Product Short Description

Product Name: Schneider Electric AS-B814-108 – Modicon M340 I/O Module, 8 Analog Inputs, 4–20 mA / 0–10 V

Product Overview:
The AS-B814-108 is an 8-channel analog input module for the Modicon M340 PLC. Accepts both current (4–20 mA) and voltage (0–10 V) signals with 16-bit resolution.

Description

Technical Specifications:

Parameter Value
Channels 8 analog inputs
Input Type 4–20 mA (2-wire) / 0–10 V (3-wire)
Resolution 16-bit (65536 steps)
Accuracy (at 25°C) ±0.1% of full scale
Sampling Rate 1 ms per channel (all channels)
Isolation 500 V AC (channel-to-channel, channel-to-bus)
Common Mode Rejection 120 dB min
Power Consumption 2.5 W (bus)
Operating Temperature 0°C to +60°C
Mounting DIN rail / M340 backplane
Standards IEC 61131-2, CE, UL 508

Functional Features:

  • Dual input range: 4–20 mA or 0–10 V (configurable per channel via DIP switch)
  • 16-bit A/D converter per channel
  • Diagnostic LED per channel
  • Cold-junction compensation for thermocouple use (with external module)
  • Calibration via Unity Pro software

Material Composition:

  • Housing: Polycarbonate (PC) – UL94 V-0
  • PCB: FR-4, conformal coated
  • Terminals: Spring-clip push-in
  • Isolation: Optical isolation per channel

Structural Features:

  • 40 mm module width
  • DIP switches on front for range selection
  • LED per channel for status/fault
  • Backplane connector for M340

Working Principle:
Analog signal enters → signal conditioning (filtering, scaling) → 16-bit ADC converts → data sent via backplane to PLC CPU over Modbus/Ethernet. Isolation barrier prevents ground loops.

Advantages:

  • 16-bit resolution for high-precision measurement
  • Dual-range flexibility reduces spare parts
  • Channel-level diagnostics simplify troubleshooting

Applicable Industries:

  • Process control (chemical, water treatment)
  • HVAC monitoring
  • Energy management
  • Food & beverage

Installation Requirements:

  • Shielded twisted-pair cable for 4–20 mA signals
  • Max cable length: 300 m (4–20 mA), 50 m (0–10 V)
  • DIP switch must match sensor output type

Usage Notes:

  • Never apply voltage to current input terminals (damages module)
  • Calibrate zero and span via software before commissioning
  • Keep analog cables separated from power cables (min 100 mm)