Product Short Description

Manufacturer: Basler Electric Company (USA)

Product Overview:
The BE3-25A is a compact AC inverter drive designed for single-phase and three-phase motor control. It is engineered for pump, fan, and HVAC applications with integrated intelligence and energy-saving features.

Description

Technical Specifications:

Parameter Value
Rated Power 25 HP (18.6 kW)
Input Voltage 200–240V AC (single-phase) / 200–240V or 380–480V AC (three-phase)
Input Frequency 50/60 Hz
Output Voltage 0 to input voltage
Output Frequency 0–400 Hz
Overload Capacity 150% for 60 seconds, 200% for 3 seconds
Control Mode V/F (Scalar), Sensorless Vector
Braking Dynamic braking (internal transistor)
Communication RS-485 (Modbus RTU)
Protection Overcurrent, overvoltage, undervoltage, overtemperature, short circuit, ground fault
Enclosure Rating NEMA 1 / IP20 (indoor use)
Operating Temperature -10°C to +50°C
Dimensions Approximately 350 x 210 x 150 mm
Weight Approximately 8.5 kg

Functional Features:

  • Built-in PID controller for closed-loop process control
  • Auto-tuning function for motor parameter identification
  • Energy-saving mode with automatic V/F optimization
  • Soft start/soft stop to reduce mechanical stress
  • Multiple speed presets (up to 16 preset speeds)
  • Fault history log with up to 10 recent fault records
  • Sleep/wake function for energy conservation during idle periods

Working Principle:
The drive rectifies incoming AC power to DC using a diode bridge rectifier, then uses IGBT inverter switches to synthesize variable-frequency, variable-voltage AC output. The PWM (Pulse Width Modulation) technique controls motor speed by adjusting output frequency and voltage ratio.

Advantages:

  • Compact footprint saves panel space
  • Integrated PID eliminates need for external controller
  • Sensorless vector control provides good torque at low speeds
  • User-friendly keypad with LED display

Applicable Industries:
HVAC, water/wastewater pumping, industrial fans, compressors, material handling

Installation Requirements:

  • Mount vertically on a flat, vibration-free surface
  • Maintain minimum 100mm clearance above and below for ventilation
  • Use shielded cable for motor connection (max 50m recommended)
  • Ground the drive chassis and motor frame

Usage Notes:

  • Perform motor auto-tuning before first operation
  • Do not exceed rated current continuously
  • Install input reactor if power supply has high harmonic distortion
  • Check braking resistor requirement for high-inertia loads