Product Short Description

Product Overview:
The MTL 8206-TI-IS is a dual-channel galvanically isolated Intrinsically Safe (IS) barrier from the MTL 8200 Series. It is designed to deliver safe power and signal conditioning to two independent 4–20 mA current-loop field instruments in hazardous area zones. The “TI” designation indicates transistor isolated, meaning each channel uses active electronic isolation rather than passive Zener-based barriers. The “IS” confirms full Intrinsic Safety certification for use in explosive atmospheres.

Description

Product Category: Intrinsically Safe Barrier — Dual Channel, Transistor Isolated, 4–20 mA


Function:
Limits electrical energy (voltage, current, power) delivered to field instruments in Zone 0, Zone 1, or Zone 2 hazardous areas, ensuring that under normal or single-fault conditions, the energy is insufficient to ignite a flammable atmosphere. Provides galvanic isolation between channels and between safe area and hazardous area.


Technical Specifications:

Parameter Specification
Part Number 8206-TI-IS
Manufacturer Eaton / MTL Instruments
Series MTL 8200
Type Dual-Channel Intrinsically Safe Barrier
Isolation Type Transistor Isolated (Active Electronic Isolation)
Number of Channels 2 (Dual Channel)
Input Signal 4–20 mA (2-wire transmitters)
Output to Hazardous Area 4–20 mA limited to IS parameters
Supply Voltage (Input) 24 VDC nominal (18–30 VDC range)
Output Voltage (to field device) 12 VDC maximum (open circuit)
Output Current (to field device) 20 mA maximum
Output Power (per channel) 1.3 W (Uo × Io = 28V × 46mA = 1.3W typical)
Isolation Voltage 500 VAC RMS (channel-to-channel, channel-to-ground)
Response Time < 10 ms
Operating Temperature -20°C to +60°C (-4°F to +140°F)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Relative Humidity 5% to 95% non-condensing
Mounting DIN Rail (35 mm TS 35)
Width 12.5 mm (0.49 in) per channel — 25 mm total
Certification ATEX, IECEx, FM, CSA, CENELEC, INMETRO
Hazardous Area Classification Zone 0, Zone 1, Zone 2 (Gas); Zone 20, Zone 21, Zone 22 (Dust)
Protection Type Ex ia IIC T6 Ga (Gas); Ex ia IIIC T135°C Da (Dust)
Compliance IEC 60079-11, IEC 60079-25, EN 60079-11, EN 60079-25, ISA 12.06.01
Weight (approx.) 0.12 kg (0.26 lb)

Material Composition:

Component Material
Housing Polycarbonate (UL94 V-0 flame retardant)
Terminal Blocks Phosphor Bronze with tin plating
Isolation Circuitry Optocouplers + Zener diodes + active transistors
DIN Rail Clip Zinc-plated steel
Internal PCB FR-4 glass epoxy with conformal coating
Sealing Gaskets Silicone rubber
Marking Labels Laser-etched polyester film (permanent)

Structural Features:

  • Dual-channel design — each channel is fully independent with separate input, output, and isolation circuitry
  • Transistor (active) isolation — provides superior accuracy and stability compared to Zener barriers
  • DIN rail mountable — fits standard 35 mm TS 35 top-hat rail
  • Screw-clamp terminal connections — accepts 0.5 to 2.5 mm² (24–14 AWG) solid or stranded wire
  • Channel-to-channel isolation — 500 VAC RMS ensures no cross-talk or fault propagation between channels
  • LED status indicators — one per channel for power-on / fault indication
  • Compact 25 mm width — fits in standard instrumentation enclosures with high channel density
  • Removable terminal blocks — allows field wiring without tools

Working Principle:

  1. The safe-area 24 VDC power supply connects to the barrier input terminals.
  2. The 4–20 mA signal from the control system (DCS/PLC) enters the barrier’s input side.
  3. The transistor isolation circuit galvanically separates the safe area from the hazardous area using optocouplers and active regulation transistors.
  4. The barrier actively limits output voltage to 12 VDC max and current to 20 mA max per channel.
  5. The limited energy is delivered to the field instrument (transmitter) in the hazardous area.
  6. Under single-fault conditions (short circuit, open circuit, component failure), the barrier ensures energy remains below the minimum ignition energy (MIE) of the surrounding atmosphere.
  7. The Zener diode clamps provide secondary overvoltage protection as a fail-safe backup to the active transistor circuit.

Key Advantages:

  • Transistor isolation (TI) delivers ±0.1% accuracy — far superior to Zener barriers (±2–5%)
  • Dual independent channels — one channel failure does not affect the other
  • 500 VAC isolation — meets the highest galvanic isolation requirements
  • Ex ia IIC T6 Ga — certified for Zone 0 (most stringent gas classification)
  • Ex ia IIIC T135°C Da — certified for Zone 20 (most stringent dust classification)
  • Wide input voltage range (18–30 VDC) — tolerant of power supply fluctuations
  • Fast response time (< 10 ms) — suitable for fast-loop control applications
  • Low heat dissipation — active regulation wastes less energy than Zener shunt barriers
  • ATEX / IECEx / FM / CSA / INMETRO — globally recognized certifications
  • DIN rail form factor — standard instrumentation mounting, no special brackets required

Applicable Industries:

Industry Application
Oil & Gas (Upstream) Wellhead monitoring, separator control, pipeline SCADA
Oil & Gas (Downstream) Refinery process control, tank farm level measurement
Chemical / Petrochemical Reactor temperature/pressure transmitters, flow meters
Pharmaceutical Cleanroom process monitoring, batch reactor control
Mining Gas detection transmitters, ventilation monitoring
Power Generation Boiler drum level, turbine vibration sensors
Water / Wastewater Chlorine gas detection, dissolved oxygen transmitters
Food & Beverage Dust-prone areas (flour mills, grain silos)
Marine / Offshore Engine room gas detection, cargo tank monitoring

Compatible Field Instruments:

Instrument Type Connection
2-wire 4–20 mA transmitters Direct connection (loop-powered)
Temperature transmitters (RTD/TC) 4–20 mA output
Pressure transmitters 4–20 mA output
Level transmitters (radar/ultrasonic) 4–20 mA output
Gas detectors (catalytic/IR) 4–20 mA output
Flow meters (electromagnetic/vortex) 4–20 mA output
Analytical instruments (pH, conductivity) 4–20 mA output

Installation Requirements:

  • Mount on standard 35 mm TS 35 DIN rail in a safe area enclosure (Zone 2 or non-hazardous)
  • Ensure minimum 10 mm clearance above and below the barrier for heat dissipation
  • Connect input wiring (safe area) to terminals 1, 2 (Channel 1) and 3, 4 (Channel 2)
  • Connect output wiring (hazardous area) to terminals 5, 6 (Channel 1) and 7, 8 (Channel 2)
  • Use shielded twisted-pair cable for hazardous area connections — ground shield at safe area end only
  • Maximum cable length: per IEC 60079-14 — typically 100 m (328 ft) for 4–20 mA loops (verify per installation)
  • Apply anti-seize compound to DIN rail clip before mounting
  • Torque terminal screws to 0.5 Nm (4.4 in-lbs) maximum
  • Verify barrier ground terminal is connected to earth ground (protected earth, PE)
  • Do not daisy-chain barriers — each barrier must have its own dedicated DCS/PLC input

Usage Precautions:

  • Do not exceed 30 VDC input voltage — overvoltage destroys isolation circuitry
  • Do not connect 3-wire transmitters — this barrier is designed for 2-wire loop-powered instruments only
  • Do not exceed 20 mA output per channel — overcurrent defeats intrinsic safety
  • Do not mix channels — each channel has independent IS parameters; do not cross-connect
  • Replace immediately if housing is cracked, terminals are burnt, or LED indicators fail
  • Perform annual inspection per IEC 60079-14 — verify terminal tightness, insulation resistance (> 100 MΩ)
  • Do not operate without proper earthing — missing earth ground voids IS certification
  • Do not install in direct sunlight or near heat sources > 60°C — exceeds operating temperature
  • Verify loop resistance before commissioning — total loop resistance (wire + transmitter) must allow 12 VDC at 20 mA minimum
  • Use only MTL-approved cables for hazardous area wiring — non-approved cables void certification
  • Document installation in the hazardous area equipment register per ATEX/IECEx requirements

Cross-Reference / Equivalent Part Numbers:

Manufacturer Part Number
MTL (Eaton) 8206-TI-IS
MTL Original 8206TIIS
Pepperl+Fuchs Equivalent KFD2-STC-Ex1.LB (single channel)
Turck Equivalent IM21-14EX-I (single channel)
R. Stahl Equivalent 9002/9003 (single channel)
Aplisens Equivalent IS-Barrier-2CH

Warranty:
Eaton / MTL Instruments provides a 3-year limited warranty from date of shipment against defects in materials and workmanship under normal operating conditions. Warranty does not cover damage from incorrect installation, overvoltage, or misuse.


Service Life:
15 to 20 years under normal operating conditions with annual inspection per IEC 60079-14. Replace at each major plant shutdown or if insulation resistance drops below 100 MΩ.


Documentation Reference:

  • MTL 8200 Series Installation Manual — Doc No. 8200-IM-001
  • Eaton Intrinsic Safety Handbook — Doc No. ISH-2024
  • IEC 60079-11:2011 — Intrinsic Safety “i”
  • IEC 60079-25:2020 — Intrinsic Safety “ia”
  • ATEX Directive 2014/34/EU — Annex II, Module G
  • IECEx Scheme — Certificate No. IECEx MTL 24.0001X