Product Short Description
The GE IC670GBI002 is a high‑performance Bus Interface Unit (BIU) within the GE Fanuc Field Control product line. It acts as the master head module for a local I/O station, linking a host PLC or PC to a cluster of up to 8 Field Control I/O modules over the Genius serial bus. It handles all bus communication, data buffering, and power distribution to the local I/O modules. This unit supports redundant CPU configurations, hot‑swap I/O replacement, and provides comprehensive on‑board diagnostics. It is widely deployed in distributed industrial automation systems where reliable, deterministic control of remote I/O is required.
Description
Technical Specifications
- Manufacturer: GE Fanuc / Emerson Automation
- Part Number: IC670GBI002
- Product Type: Genius Bus Interface Unit (BIU)
- Compatible System: GE Field Control I/O, Genius Network, Series 90‑30/70 PLCs
- I/O Capacity: Up to 8 Field Control I/O modules per BIU
- Data Exchange: 128 bytes input / 128 bytes output per bus scan
- Communication Protocol: Genius Protocol (deterministic token‑passing)
- Baud Rate: Configurable up to 153.6 kbps
- Power Input: 18–30 VDC (nominal 24 VDC); 115 VAC optional
- Power Consumption: 16.8 W maximum at full load
- Inrush Current: 15–50 A peak, 3 ms maximum duration
- Backplane Power Output: 6.5 VDC ±5%, up to 1.4 A (24 VDC input)
- Holdup Time: 10 ms minimum
- Isolation: 1500 VAC for 1 minute (bus to logic); 250 VAC continuous
- LED Indicators: PWR, RUN, COM, FAULT
- Operating Temperature: 0°C to +55°C (32°F to 131°F)
- Storage Temperature: -40°C to +85°C (-40°F to 185°F)
- Humidity: 5%–95% RH, non‑condensing
- MTBF: 183,000 hours
- Mounting: Standard DIN rail or panel mount
- Dimensions: 100 mm × 60 mm × 125 mm (3.9” × 2.4” × 4.9”)
- Weight: 0.68 kg (1.5 lbs)
- Certifications: CE, UL, CSA, RoHS
Key Features
1. Centralized Genius Bus Communication
- Serves as the local bus master for up to 8 I/O modules, managing all token‑passing communication on the Genius network.
- Exchanges 128 bytes input / 128 bytes output per scan, supporting high‑density analog and discrete I/O applications.
- Supports 153.6 kbps maximum baud rate for fast, deterministic data transfer in real‑time control systems.
2. Integrated Power Distribution
- Derives primary power from an external 24 VDC source (18–30 VDC range).
- Supplies 6.5 VDC backplane power to all connected I/O modules, eliminating the need for separate power supplies in the I/O station.
- Features 10 ms holdup time to maintain operation during brief power sags.
3. Redundancy & High Availability
- Supports hot‑standby CPU redundancy on the Genius bus, enabling seamless failover to a backup controller without process interruption.
- Compatible with ** Genius bus redundancy** configurations for mission‑critical applications.
4. Hot‑Swap & Maintainability
- Enables hot‑swap replacement of individual I/O modules (with compatible terminal blocks), allowing maintenance without shutting down the station or Genius network.
- Four on‑board LEDs (PWR, RUN, COM, FAULT) provide immediate visual status of power, operation, communication, and fault conditions.
5. Advanced Diagnostics & Protection
- Detects and reports module‑level faults (loss of communication, I/O errors, overvoltage/overcurrent) to the host PLC.
- Provides fault logging and status reporting for predictive maintenance.
- Industrial‑grade EMI/RFI shielding and electrical isolation protect against noise, spikes, and ground loops in harsh environments.
6. Compact & Flexible Installation
- DIN‑rail mountable with a compact footprint, saving cabinet space.
- Supports panel‑mount alternative for customized control cabinet layouts.
Applications
- Process Industries: Chemical, petrochemical, and pharmaceutical plants for distributed control of reactors, pumps, valves, and analytical instruments.
- Power Generation: Fossil and renewable power plants for boiler controls, turbine auxiliary systems, and balance‑of‑plant monitoring.
- Oil & Gas: Refineries, pipelines, and offshore platforms for monitoring pressure, flow, temperature, and controlling pumping and safety shutdown systems.
- Water & Wastewater: Treatment facilities for controlling pumps, blowers, valves, and monitoring water quality parameters (pH, dissolved oxygen, turbidity).
- Manufacturing: Automotive, food and beverage, and packaging lines for high‑speed assembly, material handling, and machine safety systems.







Reviews
There are no reviews yet.