Product Short Description
Technical Specifications:
- Electrical Parameters
- Nominal Output Voltage: 24 VDC
- Operating Voltage Range: 15 VDC to 30 VDC
- Absolute Maximum Output Voltage: 33 VDC
- Absolute Maximum Reverse Input Voltage: -0.6 VDC
- On-State Voltage Drop (Typical): 1.0 VDC at 1.5 A
- Per-Point Maximum Current Rating: 0.7 A
- Typical Switching Current: 3.0 A
- Surge Current (10 ms Duration): 4.8 A
- Self-Limiting Switching Current: 4.8 A
- Degraded Mode Typical Current: 1.5 A
- Degraded Mode Self-Limiting Current: 0.7 A
- Minimum Load Current Requirement: 30 mA
- Maximum Load Leakage Current: 4 mA
Description
-
- Physical Parameters
- Dimensions (W×H×D): 228 mm × 178 mm × 112 mm
- Net Weight: 2.75 kg
- Environmental Parameters
- Operating Temperature Range: -40°C to +70°C
- Storage Temperature Range: -40°C to +85°C
- Relative Humidity Tolerance: 5% to 95% (non-condensing)
- Isolation & Protection Parameters
- Point-to-Point Isolation Voltage: 1500 VDC
- Functional Earth to Protective Earth Isolation: ≥ 500 VDC
- Functional Earth to Logic Earth Isolation: ≥ 800 VDC
- Protection Mechanism: Self-protecting design, no external fuses required for field terminations
- Performance Parameters
- Number of Output Points: 16 commoned output channels
- Full Channel Loop-Back Scan Time: 1.0 ms
- Maximum Diagnostic Glitch Duration: 2 ms
- Typical Diagnostic Glitch Duration: 500 μs
- Maximum Output Toggle Rate: 20 ms per cycle
- Physical Parameters
- Functional Features:
- Triple Modular Redundancy (TMR) Architecture: Three independent parallel channels perform identical operations simultaneously; the module uses majority voting logic to ensure correct output even if one channel fails, eliminating single points of failure.
- Comprehensive Self-Diagnostics: Real-time continuous monitoring of channel health, voltage levels, current status, and isolation integrity; generates immediate fault alerts for any abnormal conditions to support predictive maintenance.
- Commoned Output Configuration: 16 output points share a common power supply, simplifying field wiring and reducing installation complexity while maintaining independent channel control capabilities.
- Wide Voltage Compatibility: Supports an operating voltage range of 15 VDC to 30 VDC, adapting to unstable power supply conditions in industrial sites without performance degradation.
- High Isolation Capability: 1500 VDC point-to-point isolation prevents cross-channel interference and protects the module from voltage surges in the field.
- Seamless System Integration: Fully compatible with Triconex TS3000, Tricon, and Trident safety controllers, supporting hot swapping for online module replacement without interrupting system operation.
- Application Scenarios:
- Oil & Gas Industry: Safety control systems for offshore platforms, refineries, pipeline transportation, and LNG terminals; used to control emergency shutdown valves (ESD) and fire/gas protection systems.
- Chemical & Petrochemical Industry: Critical process control for reactors, distillation towers, and hazardous material storage facilities; ensures safe shutdown in case of process deviations.
- Power Generation Industry: Boiler protection systems (BMS), turbine control systems, and nuclear power plant auxiliary systems; meets the strict safety requirements of power generation processes.
- Pharmaceutical Industry: Production line safety control for sterile manufacturing and hazardous drug processing; complies with GMP and FDA regulatory standards.
- Mining Industry: Underground mine ventilation control, conveyor belt emergency stop systems, and ore processing plant safety interlocks.