The ABB REF615E_1G (H-B-F-N-AE-AG-A-N-B-1-A-N-A-1-1G) is a high‑performance, compact intelligent electronic device (IED) from ABB’s Relion® 615 series, purpose‑built for comprehensive protection, control, measurement, and supervision of medium‑voltage (MV) overhead lines and cable feeders in utility substations and industrial power systems. It operates reliably in radial, looped, and meshed distribution networks, supporting isolated neutral, resistance‑earthed, compensated, and effectively‑earthed system configurations. Engineered for full IEC 61850 compliance, it delivers fast fault clearance, seamless communication interoperability, and flexible configuration, making it ideal for primary feeder protection and redundant backup applicationseero. Its withdrawable plug‑in design enables rapid installation, commissioning, and maintenance, while pre‑set standard configurations accelerate project deliveryeero.

Description

Technical Specifications

Core System & Performance

  • Processor: High‑speed numerical processing platform for real‑time protection and measurement
  • Sampling Rate: 32 samples per power cycle (1.2 kHz at 50 Hz) for precise fault detection
  • Operating Frequency: 45–65 Hz (supports 50/60 Hz systems)
  • Measurement Accuracy: Current ±1%; Voltage ±1%; Time ±1%
  • Setting Groups: 6 independent setting groups for flexible operational mode switching
  • Fault Recording: Disturbance recorder with 12 analog channels, 64 binary channels, and flexible triggering
  • Trip Time: Typical fault trip < 40 ms; high‑speed output option < 1 ms
  • Event Logging: 20,000+ time‑stamped events (1 ms resolution)
  • Communication Performance: GOOSE transmission time ≤3 ms for high‑speed interlocking and protection schemes

Power Supply

  • Nominal Voltage: 24–250 V DC / 110–240 V AC (universal wide‑range input)
  • Power Consumption: < 15 W (quiescent); < 20 W (operating)
  • Isolation: Full galvanic isolation between power, I/O, and communication circuits
  • Voltage Interruption Tolerance: < 50 ms without relay reset

Analog Inputs

  • Phase Current: 3 channels, programmable for 1 A or 5 A nominal (CT secondary)
  • Residual Current: 1 channel (5 A/1 A/0.2 A) for earth‑fault detection
  • Voltage Inputs: 3 phase voltage + 1 ground voltage (60–210 V AC nominal)
  • Input Impedance: < 20 mΩ (current); < 0.05 VA (voltage)
  • Thermal Withstand: Continuous 20 A; 1 s 500 A (current inputs)
  • Dynamic Withstand: Half‑wave 1250 A (current inputs)

Digital I/O

  • Binary Inputs: 8–16 galvanically isolated 24–250 V DC inputs (configurable)
  • Power Outputs: 4 heavy‑duty trip contacts (250 V AC / 30 V DC, 5 A)
  • Signal Outputs: 8–16 NO/NC configurable contacts (alarm, status, indication)
  • High‑Speed Outputs: Optional 1 ms operate‑time outputs for arc‑fault protection
  • HMI Indicators: 3 fixed LEDs (Ready, Start, Trip); 16 programmable LEDs

Communication Interfaces

  • Ethernet: 2 ports supporting IEC 61850 Ed.1/Ed.2, GOOSE, IEC 61850‑9‑2 LE, PRP, HSR
  • Serial: RS‑485 (Modbus RTU, IEC 60870‑5‑103, DNP3.0)
  • Optional: Profibus DPV1 (via SPA‑ZC 302 adapter), fiber‑optic (ST/LC)
  • Local Port: Front USB for PC configuration (PCM600 software)
  • Time Sync: IEEE 1588 V2, IRIG‑B input for high‑accuracy time stamping
  • Client Capacity: Simultaneous connection to 5 IEC 61850 clients, 5 Modbus clients, and 1 DNP3.0 client

Physical & Environmental

  • Dimensions: 233 mm (H) × 160 mm (W) × 280 mm (D)
  • Weight: Approx. 4.0 kg
  • Mounting: Plug‑in flush mounting; 4U rack compatible
  • Protection Rating: IP54 (front); IP20 (rear terminals)
  • Operating Temperature: -25 °C to +70 °C
  • Storage Temperature: -40 °C to +85 °C
  • Humidity: 5%–95% RH (non‑condensing)
  • EMC Compliance: IEC 61000 series, EN 50081‑2, CISPR 11
  • Certifications: CE, IEC 60255, IEEE C37.90, RoHS

Functional Features

Comprehensive Protection Functions

  • Directional/Non‑Directional Overcurrent: 4‑stage (50/51) with DT/IDMT characteristics (IEC/ANSI compliant)
  • Multi‑Frequency Admittance Earth‑Fault: High‑sensitivity detection for continuous, transient, and intermittent faults
  • Sensitive Earth Fault (SEF) & High‑Impedance Fault (HIZ): Detects downed conductors and low‑current earth faults
  • Thermal Overload (49): Cable/feeder thermal memory for overheating prevention
  • Phase Discontinuity (46PD) & Negative‑Sequence (46): Detects open‑phase and unbalanced loads
  • Breaker Failure Protection (50BF/51BF): Backup tripping for failed circuit breakers
  • Arc‑Fault Protection (AFD): 3 light‑sensor inputs; fast tripping for switchgear arc events
  • Auto‑Reclose (79): 1–4 programmable shots for overhead line fault restoration
  • Fault Location: Impedance‑based short‑circuit and earth‑fault location in radial networks
  • Voltage & Frequency Protection: Overvoltage, undervoltage, residual overvoltage, positive/negative sequence overvoltage, overfrequency, underfrequency, and rate‑of‑change‑of‑frequency protection

Advanced Control & Automation

  • Circuit Breaker Control: Local/remote close/trip via HMI or communication; configurable interlocking logic
  • Sequence Control: Logic gates and timers for automated switching sequences
  • Trip Circuit Supervision (TCS): Monitors breaker trip‑circuit integrity and alarms on faults
  • Breaker Condition Monitoring: Trip counter, travel time, spring charge, and wear tracking
  • Synchrocheck & Synchronization: Optional for controlled breaker closing

Monitoring & Diagnostics

  • Real‑Time Measurements: Phase/residual current/voltage, power, energy, power factor, harmonics, and unbalance
  • Disturbance Recording: Pre/post‑fault waveform capture in COMTRADE format for detailed fault analysis
  • Self‑Diagnostics: Continuous hardware/software monitoring with internal fault alarms
  • Graphical HMI: Large color display with customizable single‑line diagrams (SLDs)
  • Web‑Based Interface: Remote access for monitoring, configuration, and diagnostics

Flexibility & Integration

  • Plug‑In Design: Withdrawable unit for fast installation and maintenance
  • Modular Communication: Multi‑protocol support for seamless SCADA/DCS integration
  • Standard Configurations: 12 pre‑set setups for rapid commissioning
  • Sensor Compatibility: Works with conventional CT/VT and modern Rogowski coils
  • Redundancy: PRP/HSR support for high‑availability communication networks

Application Scenarios

Utility Distribution Networks

  • MV Feeders: Primary protection for overhead lines and underground cables in distribution substations
  • Distribution Transformers: Backup protection for pole‑mount and pad‑mount transformers
  • Capacitor Banks: Overcurrent, unbalance, and overvoltage protection for reactive power compensation
  • Sectionalizers/Reclosers: Automated control and protection for grid sectionalizing devices
  • Distributed Generation: Interconnection protection for solar, wind, and battery energy storage systems

Industrial Power Systems

  • Manufacturing Plants: Motor and feeder protection for pumps, fans, conveyors, and compressors
  • Mining Operations: Heavy‑duty protection for underground power distribution
  • Oil & Gas Facilities: Refineries, offshore platforms, and pipeline pumping stations
  • Water & Wastewater: Pump stations and treatment plant power systems
  • Data Centers: Backup power and UPS feeder protection

Specialized Applications

  • Railway Electrification: Traction power substation feeder protection
  • Marine & Offshore: Shipboard and offshore platform power distribution
  • Digital Substations: IEC 61850‑based automation with process bus (IEC 61850‑9‑2 LE) integration
  • Arc‑Fault Protection: Fast busbar and switchgear protection in metal‑enclosed cabinets
  • Retrofit Projects: Legacy system upgrade with modern protection and communication

Reviews