Product Short Description

Product Introduction

The ABB SPAJ140 C is a microprocessor-based, combined overcurrent and earth-fault protection relay, belonging to the SPACOM product family. It is designed for selective short-circuit and earth-fault protection of radial feeders in solidly-earthed, resistance-earthed, or impedance-earthed power systemsABB. This integrated unit combines phase overcurrent protection, non-directional earth-fault protection, and built-in circuit-breaker failure protection, offering flexible tripping and signaling capabilities. It features comprehensive self-supervision, local/remote parameterization, and data communication, making it a robust solution for medium-voltage distribution network protection.

Description

Technical Specifications

  • Product Type: Microprocessor-based combined overcurrent and earth-fault relay
  • Protection Functions:
    • Three-phase low-set phase overcurrent (definite time or IDMT characteristic)
    • Three-phase high-set phase overcurrent (instantaneous or definite time)
    • Low-set non-directional earth-fault (definite time or IDMT characteristic)
    • High-set non-directional earth-fault (instantaneous or definite time)
    • Built-in circuit-breaker failure protection
  • Time-Current Curves: Four standard IDMT curves (IEC/BS), plus RI and RXIDG specific inverse-time characteristics
  • Input Current Ratings: 1 A or 5 A (CT secondary)
  • Auxiliary Power Supply: Wide-range DC (24–250 V DC) or AC (100–240 V AC, 50/60 Hz)
  • Output Relays: 2 heavy-duty tripping relays + 4 light-duty signaling relays (configurable matrix)
  • Communication Interface: Serial port for local/remote access to parameters, fault logs, and diagnostics
  • Display: Numerical readout for measured values, settings, fault records, and status codes
  • Self-Supervision: Continuous hardware/software monitoring with auto-diagnosisABB
  • Operating Temperature: -10°C to +55°C
  • Humidity: 5%–95% RH (non-condensing)
  • Protection Degree: IP54 (aluminum case for harsh/offshore environments)
  • Certifications: IEC 60255, CE, UL, and marine/offshore compliance
  • Mounting: Panel-mounted or rack-mounted
  • Dimensions: Standard industrial form factor (approx. 144 mm × 144 mm × 220 mm)
  • Weight: Approx. 3.5 kg

Key Features

Integrated Multi-Protection Design

  • Combined Functionality: Integrates phase overcurrent, earth-fault, and breaker failure protection in one unit, reducing panel space and wiring complexityABB.
  • Dual Protection Stages: Each protection function includes low-set (back-up) and high-set (instantaneous) stages for selective coordination.
  • Flexible Time Characteristics: Supports both definite time and multiple IDMT curves for precise protection coordination in complex networks.

Advanced Communication & Configuration

  • Serial Connectivity: Built-in serial port enables remote parameter setting, fault data retrieval, and integration with SCADA/automation systems.
  • Local/Remote Operation: Full control via front-panel keypad/display or portable PC software.
  • Fault Memory: Records fault parameters, current values, and event logs for post-fault analysis.

Robust Reliability & Diagnostics

  • Continuous Self-Supervision: Monitors microprocessor, power supply, and I/O circuits; alerts on internal faultsABB.
  • High Electromagnetic Immunity: Designed to withstand industrial EMI, ensuring stable operation in substations.
  • IP54 Enclosure: Dust and water-resistant aluminum housing for offshore and harsh industrial sites.

Flexible Output & Control

  • Configurable Relay Matrix: Outputs can be freely assigned to trip, alarm, or status signals.
  • External Control Input: Accepts blocking signals, remote reset, or setting selection via terminal 10–11.
  • Visual Indicators: LED and numerical display for real-time status, fault codes, and measured values.

Application Scenarios

Medium-Voltage Distribution Networks

  • Radial Feeders: Primary protection for overhead lines and cables in urban/rural distribution gridsABB.
  • Substation Feeders: Selective protection in distribution substations with solid/resistance/impedance groundingABB.
  • Distribution Transformers: Backup overcurrent and earth-fault protection for distribution transformers.

Industrial Power Systems

  • Oil & Gas Facilities: Protection for pumps, compressors, and process loads in refineries and offshore platforms.
  • Mining Operations: Reliable protection for heavy machinery and conveyor systems in underground mines.
  • Manufacturing Plants: Overcurrent/earth-fault protection for motor control centers and industrial distribution boards.
  • Marine & Offshore: IP54-rated units for shipboard power distribution and offshore platform protection.

Infrastructure & Utilities

  • Water & Wastewater: Protection for pump stations and treatment plant electrical systems.
  • Renewable Energy: Grid interconnection protection for wind farms and solar power plants.
  • Railway Electrification: Feeder protection for DC/AC traction power supply systems.

Legacy System Retrofits

  • Substation Modernization: Upgrading electromechanical relays with microprocessor-based SPAJ140 C for improved selectivity and diagnostics.
  • System Expansion: Adding protection to existing distribution networks without major rewiring.

Reviews