The ABB REF620 NBFNAANNNDA1BBN1XF is a dedicated, high‑performance feeder management relay within ABB’s Relion® 620 series, engineered for comprehensive protection, control, measurement, and supervision of medium‑voltage (MV) feeders in utility distribution networks and industrial power systems. It supports radial, looped, and meshed network topologies, accommodating isolated, resistance‑earthed, compensated, and effectively‑earthed neutral configurations—including systems with distributed power generation (solar, wind, battery energy storage)ABB.
Designed for functional scalability and seamless integration, it combines advanced numerical algorithms with full IEC 61850 Ed.1/Ed.2 compliance, enabling high‑availability communication via PRP/HSR redundancy, GOOSE messaging, and IEC 61850‑9‑2 LE process bus.
Description
Technical Specifications
Core System & Performance
- Processor: High‑speed numerical processing platform for real‑time protection, control, and measurement
- Sampling Rate: 32 samples per power cycle (1.2 kHz at 50 Hz) for precise fault detection
- Operating Frequency: 45–65 Hz (supports 50/60 Hz systems)
- Measurement Accuracy: Current ±1%; Voltage ±1%; Time ±1%
- Setting Groups: 6 independent setting groups for flexible operational mode switching
- Fault Recording: Disturbance recorder with 12 analog channels, 64 binary channels, and flexible triggering
- Typical Fault Trip Time: < 40 ms; optional high‑speed outputs < 1 ms for arc‑fault protection
- Event Logging: 20,000+ time‑stamped events (1 ms resolution)
- Communication Latency: GOOSE transmission time ≤3 ms for fast interlocking schemes
Power Supply
- Nominal Voltage: 90–264 V AC / 24–250 V DC (universal wide‑range input)
- Power Consumption: < 15 W (quiescent); < 20 W (operating)
- Isolation: Full galvanic isolation between power, I/O, and communication circuits
- Voltage Interruption Tolerance: < 50 ms without relay reset
Analog Inputs
- Phase Current: 3 channels, programmable for 1 A or 5 A nominal (CT secondary)
- Residual Current: 1 channel (5 A/1 A/0.2 A) for earth‑fault detection (core balance CT compatible)
- Voltage Inputs: 3 phase voltage + 1 ground voltage (60–210 V AC nominal); 1 phase‑to‑phase input for synchrocheck
- Input Impedance: < 20 mΩ (current); < 0.05 VA (voltage)
- Thermal Withstand: Continuous 20 A; 1 s 500 A (current inputs)
- Dynamic Withstand: Half‑wave 1250 A (current inputs)
- Optional Sensor Inputs: 3 combisensor inputs (RJ‑45) for direct sensor integration
Digital I/O
- Binary Inputs: 16–24 galvanically isolated 24–250 V DC inputs (configurable; expandable via optional module)
- Power Outputs: 4 heavy‑duty trip contacts (250 V AC / 30 V DC, 5 A)
- Signal Outputs: 8–14 NO/NC configurable contacts (alarm, status, indication)
- High‑Speed Outputs: Optional 3-channel module with < 1 ms operate time for arc‑fault protection
- HMI Indicators: 3 fixed LEDs (Ready, Start, Trip); 11 dual‑color (red/green) programmable LEDs
- Local Push Buttons: 16 configurable buttons with LED indicators (local/remote switch, setting group control, disturbance trigger)
Communication Interfaces
- Ethernet: 2 ports supporting IEC 61850 Ed.1/Ed.2, GOOSE, IEC 61850‑9‑2 LE, PRP, HSR, RSTP
- Serial: RS‑485 (Modbus RTU, IEC 60870‑5‑103, DNP3.0)
- Optional: Profibus DPV1 (via SPA‑ZC 302 adapter); fiber‑optic (ST/LC)
- Local Port: Front USB for PC configuration (PCM600)
- Time Synchronization: IEEE 1588 V2 (PTP), IRIG‑B input for high‑accuracy time stamping
- Client Capacity: Simultaneous connection to 5 IEC 61850 clients, 5 Modbus clients, 1 DNP3.0 client
Physical & Environmental
- Dimensions: 233 mm (H) × 160 mm (W) × 280 mm (D)
- Weight: Approx. 4.0 kg
- Mounting: Plug‑in flush mounting; 4U rack compatible
- Protection Rating: IP54 (front); IP20 (rear terminals)
- Operating Temperature: -25 °C to +70 °C
- Storage Temperature: -40 °C to +85 °C
- Humidity: 5%–95% RH (non‑condensing)
- EMC Compliance: IEC 61000 series, EN 50081‑2, CISPR 11
- Certifications: CE, IEC 60255, IEEE C37.90, RoHS
Functional Features
Comprehensive Protection Functions
- Overcurrent Protection: 4‑stage directional/non‑directional (50/51) with DT/IDMT characteristics (IEC/ANSI compliant)
- Earth‑Fault Protection: Multi‑frequency admittance‑based (high sensitivity/selectivity), harmonics‑based, wattmetric‑based, and sensitive earth fault (SEF) detection for continuous, transient, and intermittent faultseero
- High‑Impedance Fault (HIZ): Detects downed conductors and low‑current earth faults in ungrounded systems
- Thermal Overload (49): Cable/feeder thermal memory for overheating prevention
- Phase Discontinuity (46PD) & Negative‑Sequence (46): Identifies open‑phase conditions and unbalanced loads
- Breaker Failure Protection (50BF/51BF): Backup tripping for failed circuit breakers
- Arc‑Fault Detection (AFD): 3 light‑sensor inputs for fast tripping in switchgear compartments (optional)
- Auto‑Reclose (79): 1–4 programmable shots for overhead line fault restoration
- Fault Location: Impedance‑based short‑circuit and earth‑fault location in radial networks
- Voltage & Frequency Protection: Over/undervoltage, residual overvoltage, sequence over/undervoltage, over/underfrequency, and rate‑of‑change‑of‑frequency protection
- Distributed Generation Protection: Low‑voltage ride‑through (LVRT), directional reactive power undervoltage (QU), and voltage vector shift protection (optional)
- Capacitor Bank Protection: Overload, unbalance, and resonance protection (optional)
- Busbar Protection: High‑impedance busbar protection via GOOSE messaging (no hard‑wiring required)
Advanced Control & Automation
- Circuit Breaker Control: Local/remote close/trip via HMI or communication; 3 dedicated control blocks
- Switchgear Control: 4 disconnector control blocks, 3 earthing switch control blocks, and associated position indication
- Sequence Control: Logic gates and timers for automated switching sequences
- Trip Circuit Supervision (TCS): Monitors breaker trip‑circuit integrity and alarms on faults
- Breaker Condition Monitoring: Trip counter, travel time, spring charge, and wear tracking
- Synchrocheck & Synchronization: Controlled breaker closing for parallel operation
- Interlocking Logic: Configurable to prevent unsafe equipment operations
Monitoring & Diagnostics
- Real‑Time Measurements: Phase/residual current/voltage, power, energy, power factor, harmonics, and unbalance
- Disturbance Recording: Pre/post‑fault waveform capture in COMTRADE format for forensic analysis
- Self‑Diagnostics: Continuous hardware/software monitoring with internal fault alarms
- Graphical HMI: Large color display with customizable single‑line diagrams (SLDs)
- Web‑Based Interface: Remote access for monitoring, configuration, and diagnostics
- Event & Alarm Management: 4‑level role‑based access control (viewer, operator, engineer, administrator) for secure operation
Flexibility & Integration
- Plug‑In Design: Withdrawable unit for fast replacement and maintenance
- Modular I/O: Expandable binary I/O and optional RTD/mA inputs for temperature measurement
- Multi‑Protocol Support: Seamless integration with SCADA/DCS systems (IEC 61850, Modbus, DNP3, IEC 60870‑5‑103)
- Sensor Compatibility: Works with conventional CT/VT and modern combisensors/Rogowski coils
- Redundancy: PRP/HSR support for 24/7 communication reliability
- Standard Configurations: Pre‑set templates for rapid commissioning
Application Scenarios
Utility Distribution Networks
- MV Feeders: Primary protection for overhead lines and underground cables in distribution substations
- Distribution Transformers: Backup protection for pole‑mount and pad‑mount transformers
- Capacitor Banks: Overcurrent, unbalance, and resonance protection for reactive power compensation
- Sectionalizers/Reclosers: Automated control and protection for grid sectionalizing devices
- Distributed Generation: Interconnection protection for solar, wind, and battery energy storage systems (compliant with grid codes)
- Ring/Meshed Networks: Advanced protection via interstation GOOSE communication
Industrial Power Systems
- Manufacturing Plants: Feeder and motor protection for pumps, fans, conveyors, and compressors
- Mining Operations: Heavy‑duty protection for underground power distribution
- Oil & Gas Facilities: Refineries, offshore platforms, and pipeline pumping stations
- Water & Wastewater: Pump stations and treatment plant power systems
- Data Centers: Backup power and UPS feeder protection
- Industrial Complexes: Comprehensive protection for multiple feeders and switchgear arrays
Specialized Applications
- Railway Electrification: Traction power substation feeder protection
- Marine & Offshore: Shipboard and offshore platform power distribution (wide temperature range)
- Digital Substations: IEC 61850‑based automation with process bus integration
- Arc‑Fault Protection: Fast busbar and switchgear protection in metal‑enclosed cabinets
- Retrofit Projects: Legacy system upgrade with modern protection and communication capabilities