Product Short Description

Product Name
DX522 Digital Input/Output Module, S500 I/O (8 DI / 8 Relay DO)
Product Overview
The DX522 is a mixed digital I/O module of the ABB AC500 / S500 family combining 8 digital inputs with 8 relay outputs on one module. The relay outputs switch voltages up to 230 V AC at 3 A, so the module directly interfaces low-voltage control logic with mains-powered actuators.

Description

Technical Specifications
Digital inputs: 8 channels, 24 V DC, 5 mA input current, input voltage 0–30 V, delay 0.1–32 ms
Digital outputs: 8 relay outputs (changeover), 230 V AC / 3 A, output voltage range 195.5–276 V AC, usable from 24 V up to 230 V AC/DC
Module supply: 24 V DC (20.4–28.8 V DC)
Hardware counters: 2, up to 50 kHz input frequency
Wiring: 2-wire or 3-wire connection
Protection degree: IP20
Operating temperature: 0 to +60 °C; storage −40 to +70 °C
Mounting: DIN rail TH35-15 per IEC 60715, horizontal (vertical with derating)
Dimensions: 67.5 x 76 x 62 mm (W x H x D)
Net weight: approx. 0.18 kg
Programming software: AC500 Control Builder PS501
EAN: 4016779649186
Key Features
Relay outputs provide potential-free contacts and direct switching of mains loads. Integrated hardware counters (2 channels, 50 kHz) support fast pulse evaluation. LED indication for channel status and module diagnostics. Galvanic isolation between inputs, outputs and logic. Compact 67.5 mm footprint.
Applications
Switching of contactors, solenoid valves, lamps and small motors, burner and HVAC control, packaging and conveyor systems, water/wastewater plants, and any AC500 installation requiring mains-level switching from the control system.
Working Principle
Input channels capture 24 V DC field signals with filtering and electrical isolation and pass them to the CPU via the I/O bus. On command from the CPU, the relay driver stages switch the corresponding relay contacts, providing galvanically separated outputs for AC or DC loads.
Installation Notes
Plug the module onto a suitable S500 terminal unit (e.g., TU531/TU532 for relay output modules with 230 V AC distribution, or 24 V DC bases where only signal wiring is required). Observe the maximum operating altitude of 2000 m and the horizontal mounting position for full rating.
Usage Precautions
Relay outputs are rated 3 A; inductive loads (contactors, solenoids) require appropriate arc suppression such as RC snubbers or flyback diodes. Do not mix mains and SELV circuits within one cable group. Do not exceed the total simultaneous output current of the module.

Reviews

There are no reviews yet.

Be the first to review “ABB DX522 1SAP245200R0001”

Your email address will not be published. Required fields are marked *

View Related Products