Product Short Description
Product Overview
The 3BHB022684R0101 is an air-to-air heat exchanger, type LT-5165-UL, supplied by ABB for the ACS 6000 medium-voltage drive family. It removes heat from the drive’s closed control-cabinet air circuit by transferring it to the ambient air without exchanging the internal and external air streams, keeping the electronics enclosure clean while maintaining its internal temperature.
Description
Technical Specifications
Type designation LT-5165-UL; catalog description Heat Exchanger Air/Air. Product net weight 50–65 kg depending on series; outline dimensions approximately 750 mm wide × 320 mm deep × 1025 mm high. Country of origin Switzerland; customs tariff number 84195080. Replaces previous product ID 3BHB022684R0001 (LT-5165). Associated spare parts: 3BHB024537R0101 (control board for LT-5165 type SC1000) and 3BHB024538R0101 (fan EBM R2E225-RA92-15). For deliveries from 2023 onward a new production badge model applies, with height increased from 317 mm to 350 mm.
Functional Features
Separate internal and external air circuits — the sealed cabinet loop stays dust-free while heat crosses the aluminum core; UL certification confirming compliance with Underwriters Laboratories safety standards for electrical equipment; integrated fan sets on both air sides for forced convection; control interface through the dedicated SC1000 control board for monitoring and alarm signaling.
Applications
Cabinet cooling of ABB ACS 6000 medium-voltage drive installations in electrical rooms, converter houses of mining hoists, rolling mills and other heavy-industry plants where the power and control cubicles dissipate substantial heat and a closed, filtered cabinet environment is required.
Material Composition
Aluminum plate heat-exchange core with folded-sheet steel housing, two independent fan sets with electric motors, air filters on the ambient-air intake, control board and terminal compartment for the electrical connections.
Structure and Characteristics
Rectangular cabinet-top or side-mount unit with two physically separated airflow paths: the internal (cabinet) air is drawn through the heat-exchange core by internal fans and returned cooled to the enclosure, while external fans draw ambient air through the opposite side of the core and exhaust it outside. The SC1000 control board supervises fan operation and thermal conditions.
Working Principle
Heat conduction transfers thermal energy from the warm internal air through the aluminum core plates to the cooler ambient air stream. Because the two airflows never mix, the IP rating and cleanliness of the drive cabinet are preserved while continuous heat extraction holds the internal temperature within the allowable range for the power electronics.
Installation Requirements
Mount the unit on the prepared cabinet opening with the gasket seal intact, connect the internal and external air ducts or grilles, wire the fans and the SC1000 control board to the documented terminals, and set the control parameters (fan control, alarm thresholds) per the ACS6000 cabinet documentation before commissioning.
Precautions
Keep the ambient-air filters clean and replace them at the maintenance interval, since clogged filters reduce cooling capacity and overheat the converter. Check both fan sets (spare fan 3BHB024538R0101, EBM R2E225-RA92-15) and the control board 3BHB024537R0101 during scheduled maintenance. Note the dimensional change on post-2023 production units (317 mm to 350 mm height) when planning replacement in tightly fitted installations, and always order against product ID 3BHB022684R0101.