Product Short Description
Product Introduction:
The IC200ALG328J is a 12-channel single-ended current-sourcing analog output module from GE’s VersaMax I/O series, converting digital controller data into 4–20 mA (default) or 0–20 mA (jumper-configurable) industrial current signals. It features 13-bit resolution, 20.38 mA overrange capacity, and requires external 18–30 VDC field power. The module integrates with VersaMax I/O carriers, uses LED indicators (FLD PWR, OK) for status/diagnostics, and supports loss of user-side power detection and configurable power loss response (last state retention or low-end default).
Description
- Technical Specifications:
- Output Channels: 12 single-ended current-sourcing outputs (single group, shared common)
- Output Signal: 4–20 mA (default) / 0–20 mA (jumper-configurable); Over-range capacity up to 20.38 mA
- Resolution: 13 bits (8192 discrete levels); 1.953 µA per count (4–20 mA); 2.441 µA per count (0–20 mA)
- Update Rate: 15 ms maximum per module
- Accuracy: ±0.3% typical full scale at 25°C; ±1% maximum full scale (0–60°C)
- Power Requirements: External field power 18–30 VDC (24 VDC nominal); 2 A max inrush, 100 mA max (no load), 270 mA max (all 12 outputs full scale); Backplane 5 VDC (50 mA max)
- Output Impedance: Drives up to 600 Ohms (24 VDC supply)
- Isolation: 250 VAC continuous / 1500 VAC for 1 minute (output-to-logic/frame ground)
- Diagnostics: Loss of user-side power detection; LED indicators (FLD PWR, OK)
- Power Loss Response: Jumper-configurable (last state retention or low-end default)
- Environmental Ratings: Operating temperature 0°C to +60°C; Storage temperature -40°C to +85°C; Humidity 5%–95% (non-condensing)
- Dimensions: Standard VersaMax module form factor; Weight 0.2 kg (0.44 lbs)
- Module ID: FFFF9009
- Function Features:
- 12 Single-Ended Channels: Single group with shared common for streamlined wiring
- 13-Bit Resolution: 8192 discrete levels for precise control in process automation
- Jumper-Configurable Ranges: 4–20 mA (default) / 0–20 mA via field terminal jumper
- Overrange Capacity: 20.38 mA per channel for edge-case control scenarios
- Configurable Power Loss Response: Jumper selects last state retention or low-end default for fault safety
- Integrated Diagnostics: Loss of user-side power detection and LED indicators (FLD PWR, OK) for quick status checks
- Seamless Integration: Works with VersaMax I/O carriers (IC200CHS series) for modular I/O expansion
- High Load Driving: Drives up to 600 Ohms per channel (24 VDC supply) for diverse industrial loads
- Application Scenarios:
- Process Control: Drives control valves, VFDs, and actuators in chemical, oil/gas, and water treatment plants using 4–20 mA signals
- Manufacturing Automation: Provides precise current outputs for proportional control of hydraulic/pneumatic valves, motor speed controllers, and quality control actuators in automotive, packaging, and assembly lines
- Power Generation/Distribution: Controls grid equipment (circuit breakers, tap changers) and generator excitation systems via 4–20 mA command signals
- Building Automation: Operates HVAC dampers, lighting dimmers, and energy management actuators in commercial and industrial facilities
- Material Handling: Controls conveyor speed, crane positioning, and automated storage system actuators for precise motion control
- Installation & Maintenance:
- Mounting: Install on VersaMax I/O carriers (IC200CHS001/002/005/022/025) with auxiliary terminal strips (IC200TBM series) for wiring
- Configuration: Set field terminal jumper for 4–20 mA/0–20 mA and power loss response before power-up
- Wiring: Use single-ended wiring with shielded cables; ground shields at source or module via auxiliary terminal
- Maintenance: No scheduled replacement parts; check LED indicators for field power and module status; verify power loss response during commissioning
- Replacement: Direct drop-in for IC200ALG328J; retains configuration via jumper settings and backplane communication