Product Short Description
- Technical Specifications
- Electrical Parameters: The operating voltage is 24V AC with a working frequency of 60Hz. The maximum valve load it supports is 1A for the pilot valve and 2A for the main valve at 24V AC. It adopts a single-rod flame sensing design and is compatible with typical gas controls such as VR8204, VR8304, and VR8440, as well as ignition hardware including Q345, Q3451, and Q3452.
- Timing Parameters: It has no pre-purge phase before ignition. Each ignition trial lasts 90 seconds, and it adopts a continuous retry ignition sequence without lockout timing. After an ignition failure, it will start the next ignition attempt after a 5-minute delay. The maximum response time for flame failure is 2 seconds, ensuring quick handling of abnormal flame conditions.
- Physical Parameters: The product weighs 0.39 pounds. It has a height of 4.4 inches, and its compact size allows it to be easily installed in the narrow control compartments of various heating appliances. The spark cable adapters included in the package match the connection standards of multiple old modules, facilitating direct replacement.
- Environmental Parameters: The ambient operating temperature range is from -40°F to 175°F, which is equivalent to -40°C to 79°C. This wide temperature adaptation range enables it to work normally in extremely cold outdoor equipment rooms and high-temperature internal spaces of heating appliances.
Description
- Functional Features
- Continuous Retry for Stable Ignition: The continuous retry ignition design with a 5-minute delay after failure avoids heating interruptions caused by occasional ignition failures due to unstable gas supply or temporary component sensitivity. It keeps attempting ignition until the heating equipment starts successfully or the heat demand signal is stopped, significantly improving the ignition success rate.
- Rapid Flame Safety Protection: With a maximum flame failure response time of 2 seconds, the module can immediately trigger the safety shutoff function once it detects flame extinguishment or abnormal combustion. It cuts off the gas supply to both the pilot valve and the main valve promptly, completely eliminating potential hazards such as gas leakage and subsequent explosions.
- Easy Retrofit and Replacement: It is a functional equivalent to Honeywell’s S86, S860, and S90 modules. The equipped spark cable adapters allow on-site replacement of these old modules without changing the existing spark cables. This compatibility not only simplifies the replacement process but also reduces the cost of retrofitting heating equipment control systems.
- Reliable Certification and Compliance: The module holds CSA design certification, which proves its compliance with strict industry safety and performance standards. Its electrical circuit design and material selection meet relevant industrial regulations, ensuring stable operation without malfunctions during long-term use in various heating scenarios.
- Application Scenarios
- Residential Gas Furnaces: It is widely used in residential central gas furnaces. It controls the ignition process of the furnace and monitors the flame during operation. When the indoor temperature is lower than the set value, it starts the ignition procedure to provide heating, and shuts down safely when the temperature meets the requirements, ensuring a stable and safe heating environment for families.
- Commercial Small-Scale Boilers: In small commercial places such as community clinics, small hotels, and office buildings, it is installed in small gas boilers that supply hot water and heating. It maintains the continuous and stable operation of the boilers, meeting the demands for hot water and constant temperature environments in these places while adhering to commercial safety operation norms.
- Light Industrial Heating Equipment: For light industrial workshops that require a constant temperature environment, such as small-scale electronic component processing workshops and precision instrument assembly workshops, it is used in auxiliary gas heating systems. It ensures the heating equipment operates reliably, providing a suitable temperature foundation for the production and processing of precision products.
- Retrofit of Old Heating Systems: It is applied to the maintenance and retrofit of old gas heating equipment in both residential and commercial buildings. It serves as a replacement for outdated ignition modules such as S86 and S860. It restores the safe ignition and flame monitoring functions of aging heating equipment, extending the service life of the equipment without the need for overall replacement of the heating system.
Be the first to review “Honeywell S8610M3009 One-Rod Intermittent Pilot Ignition Control Module” Cancel reply





Reviews
There are no reviews yet.