Product Short Description

Product Name
CT-APS.22S Electronic Time Relay, OFF-Delay, 2 C/O Contacts
Product Overview
The CT-APS.22S is a single-function electronic timer from ABB’s CT-S series providing an off-delay (delay-on-break) function with auxiliary-voltage-triggered timing. Ten selectable time ranges cover 0.05 seconds to 300 hours. The “2” variant offers two changeover contacts and screw terminals in a 22.5 mm housing.

Description

Technical Specifications
Function: OFF-delay with auxiliary voltage (true delay on de-energization)
Time ranges: 10 selectable ranges, 0.05 s – 300 h
Rated control supply voltage: 24–240 V AC (50/60 Hz) and 24–48 V DC, wide-range input
Trigger input: voltage-dependent control input starts the timing
Output contacts: 2 x changeover (C/O), delayed, rated 250 V AC / 6 A
Housing width: 22.5 mm
Connections: screw terminals
Indication: 2 LEDs for status indication
Mounting: DIN rail (top-hat rail), free mounting and removal with tool
Approvals: UL 508, CAN/CSA C22.2 No. 14, GL, GOST, CB Scheme, CCC, CE, C-Tick
Key Features
Wide-range supply from 24 to 240 V AC and 24 to 48 V DC covers most control voltages without variant changes. Precise front adjustment of the time value. Housing material with high fire rating. The relay is freely removable from the DIN rail for exchange without disturbing adjacent devices.
Applications
Delaying the shutdown of fans, pumps and lubrication after motor stop, keeping control circuits alive during brief power interruptions, delayed release of brakes, and general time-sequencing in machine and building controls.
Working Principle
While control supply voltage is applied, the output relays pick up immediately. When the trigger/control input or the supply is removed, the set off-delay time elapses before the output relays drop out, providing a defined delay on break.
Installation Notes
Mount on a 35 mm top-hat DIN rail in any position within the specified ambient temperature range. Observe the minimum spacing from heat sources. Select the time range and fine-adjust the delay on the front-face potentiometer before applying load.
Usage Precautions
The off-delay function requires stored energy; the specified delay is guaranteed only within the rated supply tolerances and the specified residual-energy behavior of the device. Do not exceed the 6 A contact rating; inductive loads require contact protection.