  • Frequency Range: Operates at 25 Hz, 50 Hz, or 60 Hz.
  • Input/Output:
    • RTD Inputs: 12 programmable thermal resistance detectors for stator and bearing temperature monitoring.
    • Digital Inputs: 9 total (2 predefined for breaker status, 7 configurable for remote reset or sequence tripping).
    • Analog Inputs: 4 isolated 4–20 mA inputs for process parameter integration.
    • Output Relays: 6 form-C relays (10 A/30–250 VAC/DC, 30 A for 0.2 seconds).
    • Analog Output: 4 programmable 4–20 mA outputs.

Description

  • Communication:
    • Ports: 2 RS485 ports (Modbus RTU/DNP 3.0, up to 19200 bps), 1 front-panel RS232 port.
  • Display: 40-character vacuum fluorescent screen with keyboard for local configuration.
  • Environmental:
    • Operating Temperature: -20°C to +70°C.
    • Storage Temperature: -40°C to +85°C.
  • Mechanical:
    • Dimensions: 21.6 cm (L) × 22.4 cm (W) × 25.2 cm (H).
    • Weight: Approximately 10 kg.

Functional Features

  • Protection Functions:
    • Thermal Overload: Monitors stator and bearing temperatures via RTDs with programmable alarms and tripping.
    • Differential Protection: Detects internal faults using 7 CT inputs for phase/neutral/ground current analysis.
    • Voltage/Frequency Monitoring: Tracks under/over-voltage, under/over-frequency, and power factor deviations.
    • Event Logging: Records 150+ events (e.g., tripping, alarms) with timestamps for post-fault analysis.
  • Control Capabilities:
    • Remote Reset: Enables restarts via digital inputs or communication protocols.
    • Sequence Tripping: Supports customizable logic for cascading protection actions.
  • User Interface:
    • Local Display: Real-time values, diagnostics, and setpoints via 40-character screen and keypad.
    • Status Indicators: 22 front-panel LEDs for quick system health checks.
  • Compliance: Meets SWC, C37.990 EMI/RFI standards for immunity to electrical noise.

Application Scenarios

  • Power Generation: Protects generators in thermal, hydro, and renewable energy plants against faults and thermal stress.
  • Oil and Gas: Ensures safe operation of compressor and pump drives in upstream/downstream processes.
  • Metallurgy: Monitors rolling mill generators to prevent unplanned downtime during metal processing.
  • Industrial Automation: Integrates with DCS/SCADA systems via Modbus/DNP 3.0 for centralized monitoring in factories.
  • Marine Propulsion: Safeguards shipboard generators from voltage fluctuations and overloads in harsh environments.

Design Advantages

  • Compact Form Factor: Space-saving design simplifies installation in control panels.
  • High Reliability: Built with industrial-grade components for long-term stability in extreme conditions.
  • Flexible Configuration: Field-programmable RTDs and digital inputs adapt to diverse generator types.
  • Redundant Communication: Dual RS485 ports ensure uninterrupted data transmission to control centers.