Product Short Description
Technical Specifications
-
Measured Parameters
-
Voltage: 3-phase, 4-wire or 3-wire, 57–288 V L-N
-
Current: 0–10 A via external 5 A or 1 A CTs
-
Power & Energy: Active, reactive, apparent (import/export)
-
Harmonics: THD, individual harmonics to 63rd
-
Transient Capture: 1 µs resolution, 64 kHz sampling
-
Description
-
Accuracy
-
Voltage/Current: ±0.2 %
-
Power/Energy: ±0.5 % (Class 0.5) per IEC 62053-22
-
Harmonics: ±2 %
-
-
Communication Ports
-
RS-485 Modbus RTU & DNP3
-
Ethernet 10/100 Base-T (optional)
-
USB 2.0 service port
-
-
Digital I/O
-
2 digital inputs (status or pulse counting)
-
2 solid-state relay outputs (alarm/control)
-
-
Power Supply
-
Universal 90–250 V AC / 100–250 V DC, 20 W max
-
-
Environmental Ratings
-
Operating: –10 °C to +60 °C
-
Humidity: 5 % to 95 % RH non-condensing
-
Protection: IP54 front, IP20 rear
-
-
Mounting: DIN rail (clip included) or panel cut-out 92 mm × 92 mm
Functional Features
-
Waveform Capture: 8-cycle pre- and post-trigger storage for fault analysis
-
Real-Time Clock: Battery-backed for time-stamped events and energy profiles
-
Data Logging: 1 MB internal memory for trend logs and SOE records
-
Self-Diagnostics: Automatic zero-drift check and CT/PT supervision alarms
-
Firmware Update: USB or Ethernet flash upgrade without opening enclosure
Application Scenarios
-
Utility Substations: Revenue metering, power-quality monitoring, and grid-code compliance
-
Industrial Plants: Motor control centers, steel mills, data centers for energy management and harmonic mitigation
-
Renewable Installations: Solar and wind farms for PQ analysis and grid interconnection studies
-
Commercial Buildings: Tenant sub-metering, demand response, and fault detection in high-rise facilities