Description
Technical Specifications
- Brand: ASCO
- Model: D03ATSA30200LG
- Series: 300
- Frame: D-Frame
- Poles: 3
- Phase: 3-phase
- Rated Current: 200 A
- Voltage Options: 208 / 240 / 480 / 600 V
- Frequency: 60 Hz
- Transition Type: open transition
- Withstand Rating with Breaker: 65 kA @ 240 V, 25 kA @ 480 V, 10 kA @ 600 V
- Withstand Rating with Fuse: 200 kA @ 480 V
- Enclosure Options: NEMA 1 indoor, NEMA 3R outdoor
- Lug Range: #14 to 4/0 AWG copper
Function Features
- True double-throw mechanism
- Single-solenoid operation
- Source availability detection
- Weekly exerciser function
- Control and status display
Structure Features
- Interlocked contact mechanism
- Compact D-frame design
- Solid neutral termination standard
Working Principle
- Monitors normal and emergency source
- Transfers load when preferred source fails
- Returns load after stable power restoration
Application Scenarios
- Hospitals
- Telecom facilities
- Municipal infrastructure
- Commercial buildings
- Industrial standby power systems
Installation Requirements
- Install per UL 1008 and NEC requirements
- Use properly sized copper lugs and torque settings
- Provide adequate ventilation for enclosure type
Usage Notes
- Test transfer logic periodically
- Do not bypass interlock mechanisms
- Only qualified electricians should service the switch