Product Short Description
Product Name: UES815S-24AR Universal Analog Input Terminal Module
Product Introduction: Passive 24-channel terminal module for EPRO MMS6000 machinery protection and condition monitoring systems; used to connect vibration, displacement, speed, and temperature sensors to monitoring cards.
Technical Specifications:
- Channels: 24
Description
- Type: Passive terminal module
- Compatible System: EPRO MMS6000
- Supported Cards: MMS6810 / MMS6820 / MMS6850 / MMS6860
- Input Modes: Differential / single-ended
- Terminals: Plug-in screw or spring type
- Protection: IP20
Functional Features:
- Mixed sensor support on one module
- Short signal path
- Channel labeling windows
- Cabinet DIN rail mounting
- Maintenance without full system shutdown
Application Scenarios:
- Turbine monitoring
- Compressor protection
- Rotating machinery condition monitoring
- Vibration and temperature signal marshalling
- Power plant and petrochemical asset monitoring
Performance Parameters:
- Eddy-current probe supply: −24 V
- IEPE support: external constant-current source required
- RTD support: Pt100 / Pt1000
- Current support: 4–20 mA / 0–20 mA
- Voltage support: ±10 V
Material Composition:
- Housing: molded industrial plastic
- Terminals: copper alloy, tin/nickel plated
- PCB: FR-4
- Label windows: transparent polymer
Structural Characteristics:
- Compact terminal block body
- Channel-by-channel wiring
- Direct mount in front of I/O card
- Clear channel identification
Working Principle:
The module provides wired termination and signal routing from field sensors to the monitoring card; it does not actively condition signals but ensures correct supply, shielding, and electrical connection.
Installation Requirements:
- Confirm MMS68xx card revision
- Use shielded sensor cables
- Ground shield at cabinet side
- Mount near corresponding I/O card
- Label each channel before energizing
Usage Precautions:
- Do not swap with incompatible terminal modules
- Avoid incorrect probe polarity
- Prevent moisture in cabinet
- Verify loop power for active transmitters
- Perform functional test after wiring changes





Reviews