Description
- Output Ranges: 4–20 mA DC default, 0–20 mA, 0–10 V DC
- Accuracy: ±0.1 % FS (4–20 mA), ±0.05 % drift 0–60 °C
- Load: 250 Ω max (4–20 mA), 1 kΩ min (0–10 V)
- Isolation: 1500 V DC ch-to-backplane, 500 V DC ch-to-ch
- Response: <10 ms to 99 % of step, <5 ms fault detect
- Power: 24 V DC Ovation backplane
- Operating Temp: 0–60 °C
- Dimensions: 140 × 32 × 305 mm, 0.5 kg
- Certifications: UL 61010-1, CSA 61010-1, IEC 61131-3, CE, RoHS
Functional Features: Channel-level open-load/output-fault diagnostics, HART loop compatible, hot-swappable tool-less latch, software range per channel.
Application Scenarios: Boiler feedwater valve control, damper actuators, VFD speed command, analyzer sampling sequence in power and process DCS.
Structure & Material: Ovation 1U I/O card, isolated DC/DC per bank, plastic shell, metal backplane.
Working Principle: Controller writes output value; per-channel DAC drives isolated current/voltage stage; fault comparator watches load current and reports back.
Installation Requirements: Ovation I/O chassis 1U slot, STP wiring, shield grounded at cabinet bar only, total loop R ≤ 250 Ω for mA.
Usage Notes: Hot-swap allowed with chassis powered. Do not exceed 250 Ω or output clips. Configure range in Ovation engineering station before field cutover.