Technical Specifications:
- Supported Protocol: PROFIBUS-DP-V0
- Communication Profile: DRIVECOM profile “Drive technology 20” (can be deactivated)
- Baud Rate: 9.6 kbps to 12 Mbps (automatic detection)
- Network Topology: Line (without repeaters); line or tree (with repeaters)
- Max. Number of Bus Devices: 32 per segment (standard); up to 125 with repeaters
- Max. Cable Length: Up to 1200 m per segment (depending on baud rate and cable type)
- Process Data: 1–10 words (16 bits/word) + 4 parameter data words
- External DC Supply: +24 V DC ±10%, max. 80 mA (maintains PROFIBUS communication even if the standard device fails)
- Protection Class: IP20 (NEMA 250 Type 1)
- Pollution Degree: 2
- Operating Temperature: Matches the connected Lenze standard device; storage -25 to +70 °C
- Features: I&M0 functionality for standard device identification, DIP switch for bus terminating resistor activation, LED status indicators (power supply, PROFIBUS connection, device connection)
- Connections: Terminal strip X3 with PROFIBUS (A/B), external 24 V supply, and CINH (controller inhibit) interface
Functional Features:
- Automatic baud rate detection across the full PROFIBUS-DP range
- External 24 V supply ensures the PROFIBUS network stays active even when the drive power fails
- DIP-switch-activated bus termination
- LED diagnostics for quick troubleshooting
Application Scenarios: Used in industrial automation systems where Lenze drives must be integrated into PROFIBUS-DP networks for centralized PLC control, particularly in manufacturing, material handling, and process control systems.
Working Principle: The module translates between the internal drive communication protocol and the PROFIBUS-DP-V0 standard. It acts as a slave node on the PROFIBUS network, exchanging process data (setpoints, actual values) and parameter data with the master PLC. The external 24 V supply powers the module independently so that network communication is maintained even if the drive’s main power is lost.
Installation Requirements: Insert into the AIF slot of a compatible Lenze 8200 vector, 8200 motec, or starttec device. Wire the PROFIBUS A/B lines to the network using proper PROFIBUS cable with shielding. If this module is at the end of a bus segment, activate the terminating resistor via the DIP switch. Provide a dedicated 24 V DC supply for the X3.2 terminal if bus-active-on-drive-failure is required.
Usage Precautions: Always use a separate, safely isolated (SELV/PELV) power supply for external voltage according to EN 61800-5-1. Ensure correct bus termination to avoid signal reflection. The module contains electrostatically sensitive components—observe ESD precautions during handling.