Product Name: AL8-2 Alarm Panel
-
Product Introduction: The DEIF AL8-2 is a compact, Q96-designed alarm panel intended for monitoring and indicating alarm conditions in industrial and marine plants. It features an intuitive push-button programming interface, eliminating the need for jumpers or other complex setup methods.
-
Technical Specifications:
-
Design: Compact Q96
-
Description
-
-
Inputs: 8 individual input channels
-
Outputs: 2 output relays (A and B) — (Note: DEIF official states 3 relay outputs, one for audible/visual alarm, two programmable)
-
Programming: Push-button, no jumpers
-
Master/Slave Configuration: Up to 5 units, max. distance between units 50 cm
-
Time Delay (Alarm Registration): 0 to 40 seconds, 1-second intervals
-
Time Limit (Output Relay Activation): 1 to 10 seconds, 1-second intervals (or unlimited)
-
Delayed Cancellation of Inhibit Function: 0 to 40 seconds, 1-second intervals
-
Cable Supervision: Requires 1 kΩ resistor across external alarm contact
-
Auxiliary Voltage: 12–48 VDC or 110 VDC (as indicated on the connection diagram)
-
LED Indicators: Green for “POWER ON” (also “DELAY OF ALARM” in programming mode), green/red for programming status and selected functions
-
Operating Temperature: Within typical industrial standards for similar devices
-
Mounting: Panel mount, with bezel and front sheet removable for programming access
-
-
Functional Features:
-
Each input channel can be individually programmed for N/O or N/C contact response.
-
Output relay A and/or B can be assigned to activate based on specific input channel alarms.
-
“Inhibit” function allows temporary disabling of specific alarm channels to prevent nuisance alarms during maintenance.
-
Cable supervision detects and indicates cable failure on input channels (requires 1 kΩ resistor).
-
Time-delayed alarm registration (0–40 s) filters out transient false alarms.
-
In master/slave configuration, alarms and horn output can be reset centrally from the master unit.
-
First alarm identification: clearly identifies the first alarm received among successive alarms for rapid troubleshooting.
-
-
Application Scenarios: Centralized alarm monitoring in industrial plants, marine applications, and other environments requiring reliable alarm annunciation. Capable of triggering external devices such as horns, lights, or other control systems.
-
Programming Interface: Three push-buttons: “CHANNEL SELECT,” “FUNCTION SELECT,” and “ENTER.” Pressing the “PRG” button enters programming mode (indicated by green “PRG” LED).
-
Usage Notes: Mount via panel mount; ensure proper cable supervision resistor (1 kΩ) is installed across external alarm contacts when cable failure detection is required. For master/slave configurations, maintain max. distance of 50 cm between units.